=3 VF control model;
=5 Step by step motor parameter detection model ;
=6 Continuous motor parameter detection model ;
=8 Theoretical calculation PI pa rameter model.
VC-Sel
=0 full-order mathematic model;
=1 voltage model;
=2 improved voltage model;
=3 improved full-order mathematic model.
FL-Limit
Flux linkage limit of motor.
WC-Set
Voltage W C.
Run-Mode
Run mode. Default is
“CVT”.
UINST
Command voltage, you need to reduce this value to 0.85 times of
Vin when inverter is stop.
F-Limit
Frequency limit, the maximum frequency that the inverter can
output. the default value is "50Hz"or"60Hz"
D-Mode
For choose the dry out protection mode. W hen water sen sor is
applied, dry protection mode should be set to detect dry
protection. Default is
“DETECT”.
D-Power
Dry protection power, which shall be reset when the load power
rating is lower than Solar pumping inverter. Recommended value
is 40% of the rated output power of Inverter. For example, the
D-Power of 55kW pump is 22000.
D-Time
Dry out recovery time, under auto dry out mode, after the warning
of dry out and inverter shut down, the duration from shut dow n to
restart. Default value is 30. Default duration is 30 minutes.
T-DJ
Dry checking time (Unit is S).
OF-F
For choose over flow warning function. Default is no overflow