31
Notice
!
If you select overflow protection water level sensor, you need to set the value of
“OF-F”, the LCD menu ”Settings” "Para Set" "OF-F" to modify to
“ON”. The setting method with reference to
“
8.3.5 Key Parameters of the
System Set
”.
If you selected water level sensor A, then water sensor installation method is shown below:
B1 connect SY_IN
B2 connect COM
A2 connect COM
A1 connect DG_IN
Note: Both yellow shrub-
like hammer, you need
filled water, when you
install sensor A
Figure6-7
The detail figure of Sensor A