Note:
If the relay terminal is connected to an AC 220V voltage signal, the current must be limited
within 3A.
4.3.3 Inverter Application Wiring Mode
In order to reduce the interference to the control signal and the attenuation of the signal itself,
the length of the control cable should be limited within 50m, and the distance between the control
cable and the motor cable should be greater than 0.3m.
Control cables must be shielded cables, and analog signal cables use twisted-pair shielded
wires.
Figure 4- 3 FC100P control terminal wiring diagram
Digital input terminal (DI) wiring
Source (drain) method
When using the internal 24V power supply of the inverter, the external controller is NPN type,
PNP type common emitter output wiring mode, as shown in Figure 4 -4 (J4 jumper on the left is NPN
input, J4 jumper on the left PNP input on the right ).
4
Janson Controls Technologies(Shenzhen) Co.,Limited
Chapter4 Electrical Installation
FC100P Series Manual V1.0
-16
AO2
AO2
10V
COM
DI1
DI2
DI3
DI4
DI5
+24V
OP
FC100 PLUS
DC 0-10V/0-20mA
DC 0-10V/0-20mA
1
2
3
1KΩ~5KΩ
R
S
T
R
S
T
MCCB
P(+)
PB
U
V
W
M
GND
A+
B-
AO1
GND
FM
0-24V/0-50mA
COM
Y1/AO2
GND
TC
TB
TA
RC
RB
RA
J4
COM
24V
J3
I
V
PE
J1
Y1
P(-)
Braking resistor
Three-phase 380V-440V
Input power 50/60HZ
220V power supply
to R/S terminal
digital input 1
digital input 2
digital input 3
digital input 4
high-speed pulse input 5
RS485 communication/baud rate
≤
5
.
76kbps
Analog output
0~10Vdc/0-20mA
Open collector 1
(high-speed pulse output)
Open Collector 2
Fault contact output
AC250V above 10mA and below 3A
DC30V above 10mA and below 1A
Fault contact output
AC250V above 10mA and below 3A
DC30V above 10mA and below 1A
Power supply for frequency setting
+10V 10mA
Al1 Analog input 1
Al1 Analog input 2