b0 -04
pressure stability
deviation
0
~
100.0% ( linked with
target pressure ratio )
2.0%
☆
45060
b0 -05
sleep delay
0
~
6553 . 5s ( 0 : disable
sleep)
2 0.0 s
☆
45061
b0 -06
wake up delay
0
~
6553.5s
0.0 s
☆
45062
b0 -07
Pressure upper limit
protection value
0
~
200.0% ( linked with the
target pressure ratio )
110.0%
☆
45063
b0-08
Pressure upper limit
protection shutdown
delay
0
~
6553.5s ( 0 : close
detection )
0. 3s
☆
45064
b0 -09
Lower limit frequency
exceeds target
pressure protection
delay
0
~
6553.5s ( 0 : close
detection )
3.0s
☆
45065
b0 -10
Auxiliary pump
quantity setting
0~4 (0: turn off one drag and
more)
0
☆
45066
b0 -11
Plus auxiliary pump
pressure tolerance
0
~
100.0% ( linked with
target pressure ratio )
5.0%
☆
45067
b0 -12
Add auxiliary pump
delay
0
~
6553.5s
30.0s
☆
45068
b0 -13
Minus auxiliary pump
pressure tolerance
0
~
100.0% ( linked with
target pressure ratio )
5.0%
☆
45069
b0 -14
Subtract auxiliary
pump delay
0
~
6553.5s
3 0.0 s
☆
45070
b0 -15
Pressure upper limit
emergency reduction
auxiliary pump delay
(Preempt the normal
pump down time of b
0 -1 4 )
0 ~ 6553.5s
3.0 s
☆
45071
U0 group parameter monitoring group
Function
code
Name
Setting range
Factory
default
Attrib
utes
DEC
address
U0-00
Operating frequency
(Hz)
-
0.01Hz
●
28672
U0-01
Set frequency (Hz)
-
0.01Hz
●
28673
6
Janson Controls Technologies(Shenzhen) Co.,Limited
Chapter6 Brief Introduction of Function Parameters
FC100P Series Manual V1.0
-56