Figure 4th 4 - 4 DI terminal input wiring when using internal 24V power supply
Analog input terminal (AI) wiring
AI1/AI2 can be selected as voltage input, the input range is 0-10V , the wiring is shown in Figure
4 -5 .
AI1/AI2 can be selected as current input, the input range is 0-20mA, the wiring is shown in
Figure 4 -5 .
The wiring diagram of AI2 is the same as that of AI1 .
Notice:
In order to reduce the interference and attenuation of the control signal, the length of the control
cable should be limited within 50m, and the shielding layer should be reliably grounded.
In the case of serious interference, the analog input signal needs to add filter capacitors or ferrite
magnetic rings, as shown in Figure 4 -5 .
Digital output terminal ( FM ) wiring
FM is an open-circuit collector output, which can use the internal 24V power supply of the
inverter or use an external power supply. The wiring is shown in Figure 4 -6 .
4
Janson Controls Technologies(Shenzhen) Co.,Limited
Chapter4 Electrical Installation
FC100P Series Manual V1.0
-17
1
1
5
5
24V
24V
DI1
DI1
DI5
DI5
COM
24V
OP
COM
24V
OP
COM
J4
J4
Use Internal power
PNP mode
Use Internal power
NPN mode
e
x
te
n
a
l c
o
n
tr
o
lle
r
e
x
te
n
a
l c
o
n
tr
o
lle
r
Figure 4
-
5
A11
terminal
wiring
less than 50m
relay
signal line is round 2-3 turns
in the same direction on the
ferrite magnetic ring
Ferrite magnetic ring
Filter capacitor