PA-04
PID given feedback
range
0~65535
1000
☆
64004
PA-05
Proportional gain KP1
0.0
~
100.0
20.0
☆
64005
PA-06
Integration time Ti1
0.01
~
10.00s
2.00s
☆
64006
PA-07
Derivative time Td1
0.000
~
10.000s
0.000s
☆
64007
PA-08
PID inversion cut-off
frequency
0.00
~
maximum frequency
2.00Hz
☆
64008
PA-09
PID deviation limit
0.0
~
100.0%
0.0%
☆
64009
PA-10
PID differential limiter
0.00
~
100.00%
0.10%
☆
64010
PA-11
PID given change
time
0.00
~
650.00s
0.00s
☆
64011
PA-12
PID feedback filter
time
0.00
~
60.00s
0.00s
☆
64012
PA-13
PID output filter time
0.00
~
60.00s
0.00s
☆
64013
PA-15
Proportional gain KP2
0.0
~
100.0
20.0
☆
64015
PA-16
Integration time Ti2
0.01s
~
10.00s
2.00s
☆
64016
PA-17
Derivative time Td2
0.000s
~
10.000s
0.000s
☆
64017
PA-18
PID parameter
switching condition
0: No switching
1 : Switching via DI terminal
2 : Automatic switching
according to deviation
0
☆
64018
PA-19
PID parameter
switching deviation 1
0.0%
~
PA-20
20.0%
☆
64019
PA-20
PID parameter
switching deviation 2
PA-19
~
100.0%
80.0%
☆
64020
PA-21
PID initial value
0.0
~
100.0%
0.0%
☆
64021
PA-22
PID initial value hold
time
0.00
~
650.00s
0.00s
☆
64022
PA-23
The maximum value
of the positive
direction of the two
output deviations
0.00
~
100.00%
1.00%
☆
64023
PA-24
The reverse
maximum value of
the two output
deviations
0.00
~
100.00%
1.00%
☆
64024
PA-25
PID integral attribute
Units: Integral separation
0 : Invalid
1 : Valid
Tens: Whether to stop
integration after the output
reaches the limit
0 : Continue integration
1 : Stop integration
00
☆
64025
PA-26
PID feedback loss
detection value
0.0%: no judgment feedback
loss
0.1 ~ 100.0%
0.0%
☆
64026
PA-27
PID feedback loss
detection time
0.0s
~
20.0s
0.0s
☆
64027
PA-28
PID stop operation
0: no operation when
shutdown 1: operation when
shutdown
1
☆
64028
Pb Group swing frequency, fixed length and counting
6
Janson Controls Technologies(Shenzhen) Co.,Limited
Chapter6 Brief Introduction of Function Parameters
FC100P Series Manual V1.0
-50