Basic Application Quick Start
Notice:
Some parameters have been set before leaving the factory (factory value), and you don’t need
to set them for the first time.
1. Correctly set the rated parameters of the motor
Power on, use the operation panel to set the parameters in the table below, and refer to the
motor nameplate for the motor parameters.
parameter number
parameter name
parameter number
parameter name
P1-01
Motor rated power
P1-04
Motor rated frequency
P1-02
Motor rated voltage
P1-05
Motor rated speed
P1-03
Motor rated current
2. Use the operation panel to control the start and stop and set the operating frequency
(1). Power-on. Use the operation panel to set motor parameters ( P1-01 to P1-04 ) , running
frequency ( P1-08 ) and acceleration/deceleration time ( P1-17
,
P1-18 )
.
parameter number
parameter name
set value
meaning
P0-02
Command Set Channel
Selection
0 (factory default)
Run command channel as
keyboard
P0-03
Frequency setting channel
selection
0
The operating frequency is given
by the keyboard number
Acceleration time 1
-
Acceleration time, adjust
according to actual needs
Deceleration time 1
-
Deceleration time, adjust
according to actual needs
(2). Press the key on the operation panel
to start the inverter, press
/
key to increase
/decrease the set frequency, and press the key
to stop the inverter output.
3. Use the terminal to control the start and stop and the keyboard potentiometer to set the operating
frequency
(1). Terminal DI 1 is for forward rotation signal input, DI 2 is for reverse rotation signal input, the
wiring is as shown in the figure below.
(2). Power on, and then set the function parameters according to the wiring diagram, see the
table below.
DI1
COM
K1
K2
FWD
DI2
REV
Fault indication normally closed contact
Running output indication signal
Fault indication normally open contact
Common terminal
FM
TC
TB
TA
P0-17
P0-18
- III -
STOP
RUN