Chapter 3 Mechanical Installation
3.1 Installation Precautions
•
If the parts of the inverter are incomplete or damaged, please do not install it.
•
During transportation, please use appropriate tools according to the weight of the inverter to avoid being
cut by sharp corners or being injured when the inverter rolls over or falls.
•
The inverter should be installed on flame-retardant objects such as metals, away from flammable and
explosive objects.
•
After the inverter is reliably powered off for 10 minutes, make sure that the internal charging indicator light
is off and the voltage between the power terminals (+) and (-) is lower than 36V before operating.
•
When transporting, please hold the bottom of the inverter instead of just the operation panel and cover.
•
During installation work, do not drop wires, screws, and drilling residues into the inverter.
3.2 Installation site requirements
Confirm that the installation site meets the following conditions:
•
Avoid installing in places exposed to direct sunlight, humidity, and drops of water;
•
Avoid installing in places with flammable, explosive and corrosive gases and liquids;
•
Avoid installing in places with oily dust, fibers and metal particles;
•
Install vertically on an object that is flame retardant and can bear the weight of the fuselage;
•
There is enough heat dissipation space around the inverter to ensure that the ambient
temperature is within -10-+40
℃
;
•
The installation foundation is solid, meeting the product vibration requirements, 3.5m/s
2
at 2-
9Hz, 10m/s
2
at 9-200Hz (IEC60721-3-3);
•
Installed in a place where the humidity is less than 95%RH and there is no condensation of
water droplets;
•
The protection level of the frequency inverter is IP20, and the pollution level is level 2 (dry,
non-conductive dust pollution).
Notice:
1. If the operating environment of the inverter exceeds 40
℃
, derating is required. For every
increase of 1
℃
, the inverter needs to be derated by 2%. The maximum working ambient
temperature is 50 °C .
2. Keep the ambient temperature -10-+40
℃
, install it in a well-ventilated place or add a cooling
device, which can improve the reliability of the inverter operation.
3
FC100P Series Manual V1.0
-07
Janson Controls Technologies(Shenzhen) Co.,Limited
Chapter3 Mechanical Installation
Danger