114
UMG 512
To ensure that two measurement devices achieve the same measurement results in a 10 minute
compensation interval, we recommend synchronising time measurement in the UMG 512 using
an external time signal.
m
UMG512 specifications as per IEC 61000-4-30
Characteristic
Uncertainty
Metering range
5.1 Frequency
± 10 mHz
42.5 Hz – 57.5 Hz,
51Hz – 69 Hz
5.2
Supply voltage level
± 0.1% of Udin
10% – 150% of Udin
5.3 Flicker
± 5% of measured value
0.2 – 10 Pst
5.4
Drops and excessive increases
Amplitude: ± 0.2% of Udin
Duration: ± 1 period
N/A
5.5
Voltage interruptions
Duration: ± 1 period
N/A
5.7 Unbalance
± 0.15%
0.5% – 5% u2
0.5% – 5% u0
5.8 Harmonics
IEC 61000-4-7 class 1
10% – 200% of
class 3 of IEC 61000-2-4
5.9 Interharmonics
IEC 61000-4-7 class 1
10% – 200% of
class 3 of IEC 61000-2-4
5.10
Mains signal voltage
In the range 3%-15% of Udin, ± 5% of Udin.
In the range 1%-3% of Udin, ± 0.15% of Udin.
There are no uncertainty requirements for values
< 1% of Udin.
0% – 15% of Udin
5.12
Downward/upward deviation
± 0.1% of Udin
10% – 150% of Udin
The UMG 512 meets the requirements according to IEC 61000-4-30 class A for:
• compensation, time uncertainty, marking concept, transient influence quantities.