45
UMG 512
Wiring longer than 30m must be screened.
Note the correct polarity of the supply voltage!
Digital inputs
The UMG 512 has two digital inputs. An input signal
is detected on a digital input if a voltage of at least 18V
and maximum 28V DC (typically at 4mA) is applied. There
is no input signal for a voltage of 0 to 5V and a current
less than 0.5 mA.
Fig. Connection
of digital outputs
-
+
-
+
24V DC
S1
S2
External
auxilliary voltage
14
15
16
2k21
2k21
2k21
2k21
2k21
Digital
Input 1
Digital
Input 2
UMG 512
Digital inputs 1-2
Fig. Example for the connection of external switch
contacts S1 and S2 to digital inputs 1 and 2.