62
UMG 512
Voltage transformer
You can assign voltage transformer ratios to the baseline
measurement and the supporting measurement.
Select the 400/400V setting when measuring without
a voltage transformer.
Setting range:
Primary
1 to 1000000
Secondary
1 to 999
Factory default setting:
Primary
400
Secondary 400
Rated voltage
The rated voltage corresponding to the "arranged input
voltage Udin" according to EN 61000-4-30. The rated
voltage defines the value to which
• Upward deviation (EN 61000-4-30),
• Downward deviation (EN 61000-4-30),
• Transients,
• Events and the
• Automatic scaling of graphics
refer.
Setting range:
0 to 1000000V
Factory default setting:
230V