109
UMG 512
Terminal connection capacity (digital inputs and outputs)
Rigid/flexible
0.14 - 1.5mm
2
, AWG 28-16
Flexible with core end sheath without plastic sleeve
0.25 - 1.5mm
2
Flexible with core end sheath with plastic sleeve
0.25 - 0.5mm
2
Tightening torque
0.22 - 0.25Nm
Stripping length
7mm
Potential separation and electrical safety
-
The digital inputs and outputs are double-insulated from the current and voltage measurement inputs as well as the supply voltage.
- There is only a functional insulation from the Ethernet, Profibus and RS485 interfaces and the digital I/Os, and from one another.
- The external auxiliary voltage to be connected must be compliant with SELV or PELV.
Digital outputs
2 Digital outputs with a joint earth; opto-coupler, not short-circuit proof
Supply voltage
20V - 30V DC (SELV or PELV supply)
Switching voltage
max. 60V DC
Switching current
max. 50mAeff AC/DC
Response time (Jasic program)
200ms
Switching frequency
max. 20Hz
Cable length
up to 30m unshielded, from 30m shielded
Digital inputs
2 Digital inputs with a joint earth
Maximum counter frequency
20Hz
Response time (Jasic program)
200ms
Input signal present
18V to 28V DC (typical 4mA) (SELV or PELV supply)
Input signal not present
0 to 5V DC, current less than 0.5mA
Cable length
up to 30m unshielded, from 30m shielded