110
UMG 512
RS485 interface
3-wire connection with GND, A, B
Protocol
Modbus RTU/slave, Modbus RTU/master,
Modbus RTU /Gateway
Transmission rate
9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps, 921.6kbps
Termination resistor
Can be activated by micro switch
Profibus interface
Connection
SUB D 9-pole
Protocol
Profibus DP/V0 as per EN 50170
Transmission rate
9.6k baud to 12 MBaud
Ethernet interface
Connection
RJ45
Function
Modbus gateway, embedded web server (HTTP)
Protocols
CP/IP, EMAIL (SMTP), DHCP client (BootP),
Modbus/TCP, Modbus RTU over Ethernet, FTP,
ICMP (Ping), NTP, TFTP, BACnet (option), SNMP,
Potential separation and electrical safety for the interfaces
-
The Ethernet, Profibus and RS485 interfaces are double-insulated from the current and voltage measurement inputs as well as the
supply voltage.
- There is only a functional insulation from the RCM measurement inputs and thermistor inputs as well as from the digital I/Os, and
from one another.
- The interfaces of the externally connected equipment must have double or reinforced insulation against mains voltages (acc. to
IEC 61010-1:2010).