90
UMG 512
Example: Reading the L1-N voltage
The L1-N voltage is saved in the measured value
list at address 19000. The L1-N voltage is available
in the FLOAT format.
Address = 01 is approved as the UMG 512 device
address.
The Query Message appears as follows:
Name
Hex Note
Device address
01
UMG 512, address = 1
Function
03
„Read Holding Reg.“
Start Addr. Hi
4A
19000dez = 4A38hex
Start Addr. Lo
38
Ind. Value Hi
00
2dez = 0002hex
Ind. Value Lo
02
Error Check
-
The "Response" of the UMG 512 can appear as follows:
Name
Hex Note
Device address
01
UMG 512, address = 1
Function
03
Byte meter
06
Data
00
00hex = 00dez
Data
E6
E6hex = 230dez
Error Check (CRC) -
The L1-N voltage read by address 19000 is 230V.