104
UMG 512
Technical data
General
Net weight (with attached connectors)
approx. 1080g
Device dimensions
approx. l = 144mm, w = 144mm, h = 75mm
Battery
Type Li-Mn CR2450, 3V (approval i.a.w. UL 1642)
Clock (in temperature range -40°C to 85°C)
+-5ppm (corresponding to approx. 3 minutes p.a.)
Transport and storage
The following information applies to devices which are transported or stored in the original packaging.
Free fall
1m
Temperature
-25°C to +70°C
Ambient conditions during operation
The UMG 512 is intended for weather-protected, stationary use.
The UMG 512 must be connected to the protective current connection! Protection class I in acc. with IEC 60536 (VDE 0106, Part 1).
Working temperature range
-10°C to +55°C
Relative humidity
5 to 95% RH (at 25°C without condensation)
Operating altitude
0 to 2000m above sea level
Pollution degree
2
Mounting position
vertical
Ventilation
Forced ventilation is not required.
Protection against ingress of solid foreign bodies and water
- Front side
- Rear side
IP40 i.a.w. EN60529