86
Derivative Gain
When the Gain Form setting is Parallel, this value is multiplied by the change in error
between the current reading and the previous reading to determine the derivative com-
ponent of the calculated output percent.
Reset PID Integral
The PID Integral Value is a running total of the accumulated area under the error curve
(Current Integral). When this menu option is selected, this total is set to zero and the
PID algorithm is reset to its initial state.
Minimum Output
Enter the lowest possible output value (normally 0%).
Maximum Output
Enter the highest possible output value as a percentage.
Off Mode Output
Enter the output mA value desired when the output is in Off mode, or being Interlocked,
or if the Output Time Limit has expired, or during a calibration of the sensor being used
as an input. Also if there is a Probe Wash programmed for the sensor, and the Sensor
Mode option is set to Disable the output during the Wash cycle (if the Sensor Mode op-
tion is set to Hold the output holds its last setting and the Integral is not updated during
the Wash). The acceptable range is 0 to 21 mA.
Error Output
Enter the output mA desired when the sensor is not giving the controller a valid signal.
The acceptable range is 0 to 21 mA.
Input
Select the sensor to be used by this output.
Direction
Set the control direction. This setting is used to determine the sign of the calculated
error (current process value versus set point) and allows flexible control with only posi
-
tive values for all PID tuning parameters.
Input Minimum
The low end of the sensor input range, used to normalize errors into percent of full scale
units. These values are set to the nominal range of the selected input sensor by default.
Input Maximum
The high end of the sensor input range, used to normalize errors into percent of full scale
units. These values are set to the nominal range of the selected input sensor by default.
Gain Form
Select the PID Equation Format used to enter tuning parameters.
5.3.23
Analog Output, Manual Mode
Output Details
The details for this type of output include the analog output %, HOA mode or Interlock status, accumulated on-
time, alarms related to this output, current cycle on time, and the current control mode setting.
Settings
A Manual analog output will activate if the HOA mode is Hand, or if it is Activated With another channel. There
are no additional programmable parameters
5.3.24
Analog or Relay Output, Flow Proportional Mode
ONLY AVAILABLE IF CONTROLLER INCLUDES PULSE OUTPUT OR ANALOG OUTPUT HARDWARE
Overview
In Flow Proportional control mode, the controller monitors the rate of flow through an analog or digital flow meter,
and continuously adjusts the analog output proportional band to achieve a target PPM level.
The user enters the target PPM and the data necessary to calculate the proportional band (the water flow rate at
which the maximum pulse rate will occur) required to maintain the target PPM with that flow rate of water.
% output = Target PPM
x Water Flow Rate (liter/min or gal/min)
Cycles x Pump Capacity (liter or gal/hr) x Pump Setting (%) x Specific Gravity x 166.67
% output = Target PPM
x Water Flow Rate (m3⁄min)
Cycles x Pump Capacity (liter/hr) x Pump Setting (%) x Specific Gravity x 0.16667