Type
Select the type of sensor to be connected.
5.2.6 ORP
Settings
Touch the Settings icon to view or change the settings related to the sensor.
Alarms
Low-Low, Low, High and High-High Alarms limits may be set.
Deadband
This is the Alarm Deadband. For example, if the High Alarm is 800, and the dead-
band is 10, the alarm will activate at 801 and deactivate at 790.
Reset Calibration Values
Enter this menu to reset the sensor calibration back to factory defaults.
Cal Required Alarm
To get an alarm message as a reminder to calibrate the sensor on a regular schedule,
enter the number of days between calibrations. Set it to 0 if no reminders are necessary.
Alarm & Datalog
Suppression
If any of the relays or digital inputs are selected, any alarms related to this input
will be suppressed if the selected relay or digital input is active. At the same time,
all datalogs and graphs containing the input will show no data for the duration of
the activation.
Smoothing Factor
Increase the smoothing factor percentage to dampen the response to changes. For
example, with a 10% smoothing factor, the next reading shown will consist of an
average of 10% of the previous value and 90% of the current value.
Cable Length
The controller automatically compensates for errors in the reading caused by vary-
ing the length of the cable.
Gauge
The cable length compensation depends upon the gauge of wire used to extend the cable
Name
The name used to identify the sensor may be changed.
Type
Select the type of sensor to be connected.
5.2.7 Disinfection
Settings
Touch the Settings icon to view or change the settings related to the sensor.
Alarms
Low-Low, Low, High and High-High Alarms limits may be set.
Deadband
This is the Alarm Deadband. For example, if the High Alarm is 7.00, and the dead-
band is 0.1, the alarm will activate at 7.01 and deactivate at 6.90.
Reset Calibration Values
Enter this menu to reset the sensor calibration back to factory defaults.
Cal Required Alarm
To get an alarm message as a reminder to calibrate the sensor on a regular schedule,
enter the number of days between calibrations. Set it to 0 if no reminders are necessary.
Alarm & Datalog
Suppression
If any of the relays or digital inputs are selected, any alarms related to this input
will be suppressed if the selected relay or digital input is active. At the same time,
all datalogs and graphs containing the input will show no data for the duration of
the activation.
Smoothing Factor
Increase the smoothing factor percentage to dampen the response to changes. For
example, with a 10% smoothing factor, the next reading shown will consist of an
average of 10% of the previous value and 90% of the current value.
Cable Length
The controller automatically compensates for errors in the reading caused by vary-
ing the length of the cable.
Gauge
The cable length compensation depends upon the gauge of wire used to extend the cable
Name
The name used to identify the sensor may be changed.
Sensor
Select the specific type and range of disinfection sensor to be connected.