Hold Time (Probe Wash modes)
0 seconds
3600 seconds
Max Rate (Pulse Proportional, Pulse PID modes)
10 pulses/minute
2400 pulses/minute
Minimum Output (Pulse Proportional, Pulse PID modes)
0%
100%
Maximum Output (Pulse Proportional, Pulse PID modes)
0%
100%
Gain (Pulse PID Standard mode)
0.001
1000.000
Integral Time (Pulse PID Standard mode)
0.001 seconds
1000.000 seconds
Derivative Time (Pulse PID Standard mode)us
0 seconds
1000.000 seconds
Proportional Gain (Pulse PID Parallel mode)
0.001
1000.000
Integral Gain (Pulse PID Parallel mode)
0.001 /second
1000.000 /second
Derivative Gain (Pulse PID Parallel mode)
0 seconds
1000.000 seconds
Input Minimum (Pulse PID modes)
Low end of sensor range
High end of sensor range
Input Maximum (Pulse PID modes)
Low end of sensor range
High end of sensor range
Wear Cycle Time (Lag mode)
10 seconds
23:59:59 HH:MM:SS
Delay Time (Lag mode)
0 seconds
23:59:59 HH:MM:SS
Analog (4-20 mA) Output Settings
Low Limit
High Limit
4 mA Value (Retransmit mode)
Low end of sensor range
High end of sensor range
20 mA Value (Retransmit mode)
Low end of sensor range
High end of sensor range
Hand Output
0%
100%
Set Point (Proportional, PID modes)
Low end of sensor range
High end of sensor range
Delay Time (Lag mode)
0 seconds
23:59:59 HH:MM:SS
Bleed Volume (Flow Meter Ratio mode)
1
1,000,000
Pump Capacity (Flow Prop mode)
0 gal/hour or l/hour
10,000 gal/hour or l/hour
Pump Setting (Flow Prop mode)
0% 100%
Specific Gravity (Flow Prop mode)
0 g/ml 9.999 g/ml
Target (Flow Prop mode)
0 ppm 1,000,000 ppm
Analog (4-20 mA) Output Settings
Low Limit
High Limit
4 mA Value (Retransmit mode)
Low end of sensor range
High end of sensor range
20 mA Value (Retransmit mode)
Low end of sensor range
High end of sensor range
Hand Output
0%
100%
Set Point (Proportional, PID modes)
Low end of sensor range
High end of sensor range
Proportional Band (Proportional mode)
Low end of sensor range
High end of sensor range
Minimum Output (Proportional, PID modes)
0%
100%
Maximum Output (Proportional, PID modes)
0%
100%
Off Mode Output (Proportional, PID modes, Flow Prop modes)
0 mA
21 mA
Error Output (not in Manual mode)
0 mA
21 mA
Hand Time Limit (not in Retransmit mode)
1 second
86,400 seconds (0 = unlimited)
Output Time Limit (Proportional, PID modes)
1 second
86,400 seconds (0 = unlimited)
Gain (PID, Standard mode)
0.001
1000.000
Integral Time (PID Standard mode)
0.001 seconds
1000.000 seconds
Derivative Time (PID Standard mode)
0 seconds
1000.000 seconds
Proportional Gain (PID Parallel mode)
0.001
1000.000
Integral Gain (PID Parallel mode)
0.001 /second
1000.000 /second
Derivative Gain (PID Parallel mode)
0 seconds
1000.000 seconds
Input Maximum (PID modes)
Low end of sensor range
High end of sensor range
Pump Capacity (Flow Prop mode)
0 gal/hour or l/hour
10,000 gal/hour or l/hour
Pump Setting (Flow Prop mode)
0%
100%
Specific Gravity (Flow Prop mode)
0 g/ml
9.999 g/ml