10
Target (Flow Prop mode)
0 ppm
1,000,000 ppm
Configuration settings
Low Limit
High Limit
Local Password
0000
9999
Fluent update period
1 minute
1440 minutes
Fluent reply timeout
10 seconds
60 seconds
Alarm Delay
0:00 minutes
59:59 minutes
SMTP Port
0
65535
TCP Timeout
1 second
240 seconds
Auto Dim Time
0 seconds
23:59:59 HH:MM:SS
Graph settings
Low Limit
High Limit
Low axis limit
Low end of sensor range
High end of sensor range
High axis limit
Low end of sensor range
High end of sensor range
3.0 UNPACKING & INSTALLATION
3.1 Unpacking the unit
Inspect the contents of the carton. Please notify the carrier immediately if there are any signs of damage to the controller or its
parts. Contact your distributor if any of the parts are missing. The carton should contain an Intuition-6™ Series controller and
an instruction manual. Any options or accessories will be incorporated as ordered.
3.2 Mounting the electronic enclosure
The controller is supplied with mounting holes on the enclosure. It should be wall mounted with the display at eye level,
on a vibration-free surface, utilizing all four mounting holes for maximum stability. Do not install the enclosure in a lo-
cation where it will be exposed to direct sunlight. Use M6 (1/4” diameter) fasteners that are appropriate for the substrate
material of the wall. The enclosure is NEMA 4X (IP66) rated. The maximum operating ambient temperature is 131°F
(55°C); this should be considered if installation is in a high temperature location. The enclosure requires the follow-
ing clearances:
Top: 2” (50 mm)
Left: 8” (203 mm) (not applicable for prewired models)
Right: 4” (102 mm)
Bottom: 7” (178 mm)
3.3 Immersible Copper Sensor Installation
The immersible copper sensor is designed for direct in-tank monitoring of electroless copper and microetch solutions.
By monitoring the copper content directly in the solution, control lag and hydraulic problems are eliminated.
The sensor is constructed such that a constant path length exists between the fiber optic light guides. The solution
between the light guides absorbs light at specific wavelengths in proportion to the copper concentration. The lamp and
4.8 in
122 mm
9.6 in 244 mm
5.5 in
140 mm
8.3 in
211 mm
11.1 in 282 mm
8.9 in 226 mm
6.7 in
170 mm
9.0 in 229 mm
6.8 in
173 mm
4.4 in
112 mm