DISPLAY ERROR
This alarm occurs if the user interface gets lost
Possible Cause
Correction Action
Pressing icons very quickly
Exit out of the screen and continue programming
N ETWORK CARD FAILURE
This alarm occurs if the Ethernet circuit board fails
Possible Cause
Correction Action
Ethernet card locked up
Try a power cycle to reset it
Ethernet card not seated correctly
Unplug the network card and plug it back in
Faulty Ethernet card
Replace Ethernet card
WEB SERVER FAILURE
This alarm occurs if the web server on the Ethernet circuit board fails
Possible Cause
Correction Action
Web server locked up
Try a power cycle to reset it
Faulty Ethernet card
Replace Ethernet card
Fluent DATA COMM ERROR
This alarm occurs if the controller attempts to send data to Fluent and Fluent fails to acknowledge receipt of the data
Possible Cause
Correction Action
No connection to LAN
Connect Ethernet cable to LAN
Wrong IP, subnet and/or gateway address
Program valid settings for LAN in the controller or use DHCP if
supported by the LAN
LAN is blocking outside access
Program LAN’s router to open access
Network card failure
See above
SENSOR CAL REQUIRED
This alarm occurs if the sensor’s Cal Reminder Alarm has been set to more than 0 days and if the sensor has not been calibrated
within that number of days
Possible Cause
Correction Action
Time to calibrate
Calibrate the sensor
Reminder set in error
Set the Cal Reminder Alarm to 0
CALCULATION ERROR
This alarm occurs if a virtual input calculation cannot be completed, for example if it has to divide by zero.
Possible Cause
Correction Action
Zero value for the input used as the denominator
Calibrate or evaluate that input
DI FLOW VERIFY
This alarm occurs if the control output is on but the associate flow verification device is not registering flow
Possible Cause
Correction Action
Metering pump has lost prime
Re-prime metering pump
Faulty metering pump
Repair or replace pump
Faulty verification device wiring
Correct wiring
Wrong digital input assigned to the output
Correct programming error
Faulty verification device
Repair or replace device
Faulty wiring of output to pump
Correct wiring
Faulty output board
Repair or replace board
Faulty digital input
Replace board
CONTROLLER, POWER, DISPLAY, OR SENSOR BOARD ERROR
This alarm occurs if the board listed is not recognized
Possible Cause
Correction Action
Poor ribbon cable connection
Remove and reseat ribbon cable, cycle power
Poor option card connection
Remove and reseat the board, cycle power