7.1 User Interface for Occupancy Control
Occupancy control can also be performed using the panel's touchscreen (see
). It is possible to change the occupancy mode depending on the
configurations:
OCCUPANCY_CONFIGURATION, bit 1: EDITABLE:
enables or disables the occupancy to
be edited locally from the panel;;
Modbus register: 41707;
BACnet object: MSV4, property: 4200.
How to Change the Occupancy on the Touchscreen?
Use a house button to toggle between occupied and unoccupied statuses.
A long press is not available for this feature.
7.1.1 LEDs
Value of
the OCCUPANCY_CURRENT_STATUS
parameter is presented on a house LEDs
ladder as follows:
value 0 (unoccupied):
“in house”
LED is off,
“outside”
is on;
value 1 (occupied):
“in house”
LED is on,
“outside”
is off;
value 2 (standby):
“in house”
LED is off,
“outside”
is blinking;
value 3 (forced occupied):
“in house”
LED is blinking,
“outside”
is off.