TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 41 of 49
11 List of BACnet Obejcts
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex
Object
Name
Access
Default
Value
Value
Range
Description
Device
3030
0
0x00
VERSION_TYPE
Read/
write
Shows
version and
type of the
panel and
enables 1 of
4 available
actions
Device
5101
3
0x03
RECEIVED_FRA
MES_COUNTE
R
Read-
only
0
The number
of received
Modbus
frames reset
at the start of
the panel and
at the change
of
transmission
parameters
Device
5103
5
0x05
ERROR_FRAME
S_COUNTER
Read-
only
0
The number
of received
error Modbus
frames reset
at the start of
the panel and
at the change
of
transmission
parameters
Device
5104
7
0x07
TRANSMITTED_
FRAME_COUN
TER
Read-
only
0
The number
of
transmitted
Modbus
frames reset
at the start of
the panel and
at the change
of
transmission
parameters
AI0
Present
Value
11
0x0B
LIVE_TIME
Read-
only
Uptime of the
panel in
seconds
Device
Object
Identifier
14
0x0E
BACNET_DEVIC
E_ID
Read/
write
0xFFFFFF
FF
Device's
BACnet ID
Device
3084
16
0x10
BAUD_RATE
Read/
write
11520
Sets the baud
rate