TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 45 of 49
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex
Object
Name
Access
Default
Value
Value
Range
Description
BO22
Present
Value
ECO
Switches on
an ECO LED
AO17
Present
Value
223
0xDF
EXIT_EDIT_TIM
E
Read/
write
Sets the time
after which
edition of any
editable
parameter is
finished
AO19
Present
Value
225
0xE1
CO2_SETPOIN
T_FOR_ALARM
Read/
write
1500
CO2 alarm
setpoint
AO20
Present
Value
226
0xE2
CO2_HYSTERE
SIS_FOR_ALAR
M
Read/
write
100
CO2 alarm
hysteresis
BI0
Present
Value
229
0xE5
ALARM_STATU
S
Read-
only
CO2 current
alarm status
MSV5
Present
Value
230
0xE6
NAVIGATIONA
L_LED_MODE
Read/
write
1
0-4
Sets a mode
of the
navigational
LED
AO22
Present
Value
231
0xE7
NAVIGATIONA
L_LED_BRIGHT
NESS
Read/
write
100
0-100
Navigational
LED
brightness
AO23
Present
Value
232
0xE8
NAVIGATIONA
L_LED_RED
Read/
write
100
0-100
Navigational
LED color -
red
component
intensity
AO24
Present
Value
233
0xE9
NAVIGATIONA
L_LED_GREEN
Read/
write
100
0-100
Navigational
LED color -
green
component
intensity
AO25
Present
Value
234
0xE1
0
NAVIGATIONA
L_LED_BLUE
Read/
write
100
0-100
Navigational
LED color -
blue
component
intensity
AI4
Present
Value
300
0x12
C
TEMPERATURE
_SENSOR
Read-
only
Actual
temperature
sensor value
with offset
AI5
Present
Value
301
0x12
D
HUMIDITY_SEN
SOR
Read-
only
Actual
humidity