THIRD_POINT_ACTIVE, bit 4: enables or disables decimal values in the temperature
setpoint;
Modbus register: 41513;
BACnet object: AV56, property: 4202;
Bit
Name
0
1
0
Visible
Not visible
Visible (default)
1
Editable
Not editable
Editable (default)
2
Operating mode
Changing offset
Changing setpoint (default)
3
Setpoint display
Show/change offset
(OFFSET_SETPOINT value)
Show/change effective setpoint
(EFFECTIVE_SETPOINT value)
4
ThirdPointActive
No decimal
Decimal (default)
Table 10. Temperature setpoint configuration
4.1.1 Display Brightness
Display brightness switches between three illumination modes in time:
active mode;
idle mode;
standby mode.
Figure 4. Brightness modes sequence
Active Mode Settings
BACKLIGHT_LCD_ACTIVE:
contains
a value of the LCD display brightness in the active
mode (expressed in %). The default value is 60%.
Modbus register: 40207;
BACnet object: AO3, property: Present Value;
BACKLIGHT_LCD_TIME_TO_IDLE:
allows
to set the time, after which the LCD display goes
from the active mode to idle (expressed in seconds). The default value is 10 seconds.
Modbus register: 40210;
BACnet object: AO6, property: Present Value;