TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 46 of 49
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex
Object
Name
Access
Default
Value
Value
Range
Description
sensor value
with offset
AI6
Present
Value
302
0x12
E
CO2_SENSOR
Read-
only
Actual CO2
sensor value
with offset
AI4
4205
303
0x12
F
TEMPERATURE
_SENSOR_OFF
SET
Read/
write
0
Temperature
sensor offset
AI5
4205
304
0x13
0
HUMIDITY_SEN
SOR_OFFSET
Read/
write
0
Humidity
sensor offset
AI6
4205
305
0x13
1
CO2_SENSOR_
OFFSET
Read/
write
0
CO2 sensor
offset
AI4
4003
306
0x13
2
TEMPERATURE
_FILTER
Read/
write
60
Filtering time
for the
temperature
sensor
(seconds)
AI5
4003
307
0x13
3
HUMIDITY_FILT
ER
Read/
write
60
Filtering time
for the
humidity
sensor
(seconds)
AI6
4003
308
0x13
4
CO2_FILTER
Read/
write
60
Filtering time
for the CO2
sensor
(seconds)
315
0x13
B
TEMPERATURE
_CONFIGURATI
ON
Read/
write
AI4
Out Of
Service
ACTIVE
1
Activates/
deactivates
the sensor
AI4
4202
THIRD_POINT_
ACTIVE
Sets decimal
places
316
0x13
C
HUMIDITY_CO
NFIGURATION
Read/
write
AI5
Out Of
Service
ACTIVE
1
Activates/
deactivates
the sensor
AI5
4202
THIRD_POINT_
ACTIVE
Sets decimal
places