TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 11 of 49
•
•
•
•
•
•
•
Bit
Name
0
1
0
ACTIVE
Inactive
Active (default)
4
THIRD_POINT_ACTIVE
No decimal
Decimal (default)
Table 7. Configuration of temperature sensor
HUMIDITY_CONFIGURATION:
allows
to configure the humidity sensor with two bits:
ACTIVE, bit 0: activates or deactivates the sensor;
Modbus register: 40317;
BACnet object: AI5, property: Out Of Service;
THIRD_POINT_ACTIVE, bit 4: enables or disables decimal values in the sensor;
Modbus register: 40317;
BACnet object: AI5, property: 4202;
Bit
Name
0
1
0
ACTIVE
Inactive
Active (default)
4
THIRD_POINT_ACTIVE
No decimal
Decimal (default)
Table 8. Configuration of humidity sensor
CO2_CONFIGURATION:
allows
to activate or deactivate the CO2 sensor:
ACTIVE, bit 0: activates or deactivates the sensor;
Modbus register: 40318;
BACnet object: AI6, property: Out Of Service;
Bit
Name
0
1
0
ACTIVE
Inactive
Active (default)
Table 9. Activating CO2 sensor
SETPOINT_CONFIGURATION:
allows
to configure the temperature setpoint with five bits:
VISIBLE, bit 0: enables or disables the temperature setpoint to be visible on the panel's
display;
Modbus register: 41513;
BACnet object: AV56, property: Out Of Service;
EDITABLE, bit 1: enables or disables editing of the temperature setpoint locally from
the panel;
Modbus register: 41513;
BACnet object: AV56, property: 4200;
OPERATING_MODE, bit 2: allows to set the operating mode of the temperature
setpoint configuration;
Modbus register: 41513;
BACnet object: BO55, property: Out Of Service;
SETPOINT_DISPLAY, bit 3: allows to configure the temperature setpoint display;
Modbus register: 41513;
BACnet object: BO56, property: Out Of Service;