TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 47 of 49
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex
Object
Name
Access
Default
Value
Value
Range
Description
317
0x13
D
CO2_CONFIGU
RATION
Read/
write
AI6
Out Of
Service
ACTIVE
1
Activates/
deactivates
the sensor
AO27
Present
Value
322
0x14
2
BUZZER_VOLU
ME
Read/
write
50
0-100
Buzzer
volume (%)
AO28
Present
Value
323
0x14
3
BUZZER_FREQ
UENCY
Read/
write
400
20-200
00
Buzzer
frequency
(Hz)
Device
3020
1301
0x51
5
FLASH_HW_VE
RSION
Read-
only
HW version
AV56
Present
Value
1500
0x5D
C
SETPOINT_VAL
UE
Read/
write
0-500
Temperature
setpoint
value
AI 3
Present
Value
1501
0x5D
D
EFFECTIVE_SET
POINT
Read-
only
Sum of
setpoint and
offset values
AV 57
Present
Value
1502
0x5D
E
DEFAULT_SETP
OINT
Read/
write
210
0-500
Default
temperature
setpoint
AV 58
Present
Value
1503
0x5D
F
OFFSET_SETPO
INT
Read/
write
0
0-500
Temperature
offset for
setpoint
AV 56
Low Limit
1504
0x5E
0
SETPOINT_LO
W_LIMIT
Read/
write
180
Min. available
setpoint
value
AV 56
High Limit
1505
0x5E
1
SETPOINT_HIG
H_LIMIT
Read/
write
240
Max. available
setpoint
value
AV 59
Present
Value
1506
0x5E
2
OFFSET_RANG
E
Read/
write
30
0-500
Limits offset
value
AV 56
4206
1507
0x5E
3
SETPOINT_STE
P
Read/
write
10
Setpoint step
value
1512
0x5E
8
SETPOINT_CO
NFIGURATION
Read/
write
Setpoint
configuration
of
parameters:
Visible,
Editable,
Operating