TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
page 15 of 49
•
•
•
•
•
•
•
•
•
•
Current Display Brightness
BACKLIGHT_KEYPAD:
contains a current display illumination value.
Modbus register: 30202;
BACnet object: AI2, property: Present Value.
4.3 Touchscreen
The TP panel is equipped with a touchscreen with 5 buttons for occupancy,
temperature (+/-),
and fan
(+/-) control. The
touchscreen buttons can
be activated
or
inactivated using the following parameter or in the iSMA Configurator:
DEVICE_CONFIGURATION, bit
12: KEYPAD_OFF
Modbus register: 40205;
BACnet object: BO10, property: Present Value.
Each available button operates in two modes:
short press: minimal touch time: 70 ms, maximal touch time: 400 ms;
long press: minimal touch time: 400 ms, maximal touch time: 11 s.
Functionality assigned to a given button can limit mentioned operation modes to any
combination of the two.
4.4 Navigation LED
The TP panel is equipped with a navigation LED, which allows to locate the panel in the
dark. The navigation LED can be configured using the following parameters or in the iSMA
Configurator:
NAVIGATIONAL_LED_MODE:
allows
to set a mode of the navigational LED according to
the table below:
Bit
Mode if Bit Active
0
Off
1
On (default)
2
Active on idle and standby modes
3
Active on idle mode only
4
Active on standby mode only
Table 11. Navigation LED modes
Modbus register: 30231;
BACnet object: MSV5, property: Present Value;
NAVIGATIONAL_LED_BRIGHTNESS:
allows
to set the navigational LED brightness. In the
range of 0-100%, the default value is 100%;
Modbus register: 30232;
BACnet object: AO22, property: Present Value;