TP Software User Manual

www.ismacontrolli.com

DMP253en | 1st Issue rev. 0 | 04/2022

page 43 of 49

BACnet 

Type & ID

BACnet 

Property

Decimal 

Address

Hex

Object 

Name

Access

Default 

Value

Value 

Range

Description

BO11

Present 

Value

PANEL_OFF

0

Switches the 

panel off (1)

BO12

Present 

Value

KEYPAD_OFF

0

Switches the 

panel keypad 

off (1)

AO3

Present 

Value

206

0xCE

BACKLIGHT_LC

D_ACTIVE

Read/

write

60

Contains a 

value of the 

LCD display 

illumination 

in the active 

mode 

(expressed in 

%)

AO4

Present 

Value

207

0xCF

BACKLIGHT_LC

D_IDLE

Read/

write

40

Contains a 

value of the 

LCD display 

illumination 

in the idle 

mode 

(expressed in 

%)

AO5

Present 

Value

208

0xD0

BACKLIGHT_LC

D_STANDBY

Read/

write

0

Contains a 

value of the 

LCD display 

illumination 

in the 

standby 

mode 

(expressed in 

%)

AO6

Present 

Value

209

0xD1

BACKLIGHT_LC

D_TIME_TO_ID

LE

Read/

write

10

Sets the time 

after which 

the LCD 

display goes 

from the 

active mode 

to idle 

(expressed in 

seconds)

AO7

Present 

Value

210

0xD2

BACKLIGHT_LC

D_TIME_TO_ST

ANDBY

Read/

write

5

Sets the time 

after which 

the LCD 

display goes 

from the idle 

mode to 

standby 

(expressed in 

seconds)

Содержание TP

Страница 1: ...www ismacontrolli com DMP253en 1st Issue rev 0 04 2022 TP User Manual Software ...

Страница 2: ... Display 10 4 1 1 Display Brightness 12 4 2 Keypad 13 4 2 1 Keypad Brightness 14 4 3 Touchscreen 15 4 4 Navigation LED 15 4 5 Buzzer 16 4 6 Operating User Interface 17 4 6 1 Temperature Setpoint 17 4 6 2 Fan Control 17 4 6 3 Occupancy 17 4 6 4 CO2 Alarm 18 5 Sensors Parameters 19 5 1 Temperature Sensor 19 5 2 Humidity Sensor Optional 19 5 3 CO2 Sensor Optional 20 5 4 Temperature Setpoint 20 5 4 1 ...

Страница 3: ...nual www ismacontrolli com DMP253en 1st Issue rev 0 04 2022 page 3 of 49 7 1 User Interface for Occupancy Control 29 7 1 1 LEDs 29 8 ECO 30 9 Other Parameters 31 10 List of Modbus Registers 33 11 List of BACnet Obejcts 41 ...

Страница 4: ...erent configurations of sensors temperature CO2 and humidity colors and versions with or without a display The panel is equipped with an interactive TFT touchscreen touch buttons and glass panel The panel can be configured using the iSMA Configurator software or Modbus registers BACnet objects It fits most of standard junction boxes in Europe and can easily be installed using a wall back box 1 1 R...

Страница 5: ...ch as baud rate number of data stop bits or parity bit are set using relevant Modbus registers or BACnet objects 2 1 RS485 Connection Figure 1 RS485 communication diagram 2 2 RS485 Network Termination Transmission line effects often present a problem for data communication networks These problems include reflections and signal attenuation To eliminate the presence of reflections of signal from the...

Страница 6: ... DIP switch Modbus register 30003 BACnet object N A 3 1 1 Setting MAC Address The device s MAC address can be set using one of the following methods rotary switch sets addresses from 1 9 if 0 ADDRESS decimal address 22 The Modbus register reading the address set on the rotary switch is the following ADDRESS_ROTARY_SWITCH reads the Modbus address set on the rotary switch 0 means the address is read...

Страница 7: ...ts 1 1 default 2 2 Table 4 Values of the STOP_BITS register Modbus register 40018 BACnet object N A DATA_BITS determines a number of data bits in a Modbus frame the Modbus ASCII protocol requires 7 bits Value No of Data Bits 7 7 8 8 default Table 5 Values of the DATA_BITS register Modbus register 40019 BACnet object N A PARITY_BIT each byte of data being transferred may have an additional protecti...

Страница 8: ...Modbus register 40021 BACnet object N A Incoming data frames are counted and presented through the following parameters RECEIVED_FRAMES shows the number of received frames The register s value is reset at the start of the panel and at the change of transmission parameters Modbus register 30004 BACnet object DEVICE property 5101 ERROR_FRAMES shows the number of error messages shorter than 3 or with...

Страница 9: ... sent frames The register s value is reset at the start of the panel and at the change of transmission parameters Modbus register 30008 BACnet object DEVICE property 5104 3 2 USB A USB bus is accessible through the USB C port at the bottom of the device Device identifies itself as a USB HID and can be configured using the iSMA Configurator and FCU Updater software ...

Страница 10: ...y shows measured values for all sensors available in the panel and a temperature setpoint if available with parameter s shortcut name and a proper unit Figure 3 The display sequence The display configuration parameters include the following these functions can be edited directly in the parameters or in the iSMA Configurator REFRESH_TIME sets the duration of the display time of particular parameter...

Страница 11: ...vate or deactivate the CO2 sensor ACTIVE bit 0 activates or deactivates the sensor Modbus register 40318 BACnet object AI6 property Out Of Service Bit Name 0 1 0 ACTIVE Inactive Active default Table 9 Activating CO2 sensor SETPOINT_CONFIGURATION allows to configure the temperature setpoint with five bits VISIBLE bit 0 enables or disables the temperature setpoint to be visible on the panel s displa...

Страница 12: ...T value 4 ThirdPointActive No decimal Decimal default Table 10 Temperature setpoint configuration 4 1 1 Display Brightness Display brightness switches between three illumination modes in time active mode idle mode standby mode Figure 4 Brightness modes sequence Active Mode Settings BACKLIGHT_LCD_ACTIVE contains a value of the LCD display brightness in the active mode expressed in The default value...

Страница 13: ...y brightness in the standby mode expressed in The default value is 0 Modbus register 40209 BACnet object AO5 property Present Value The panel stays in the standby mode until next user interface interaction Current Display Brightness BACKLIGHT_LCD contains a current display illumination value Modbus register 30201 BACnet object AI1 property Present Value 4 2 Keypad A front panel of the panel is equ...

Страница 14: ...object AO11 property Present Value Idle Mode Settings BACKLIGHT_KEYPAD_IDLE contains a value of the LCD display brightness in the idle mode expressed in The default value is 40 Modbus register 40213 BACnet object AO9 property Present Value BACKLIGHT_KEYPAD_TIME_TO_STANDBY allows to set the time after which the LCD display goes from the idle mode to standby expressed in seconds The default value is...

Страница 15: ...ms long press minimal touch time 400 ms maximal touch time 11 s Functionality assigned to a given button can limit mentioned operation modes to any combination of the two 4 4 Navigation LED The TP panel is equipped with a navigation LED which allows to locate the panel in the dark The navigation LED can be configured using the following parameters or in the iSMA Configurator NAVIGATIONAL_LED_MODE ...

Страница 16: ...zzer The TP panel is equipped with a buzzer which informs about a detected touch with a short sound The buzzer also provides a CO2 alarm function which emits a sounds once the CO2 level exceeds a set alarm value The alarm can be confirmed and muted by pressing any button The buzzer can be activated or inactivated using the following parameter or in the iSMA Configurator DEVICE_CONFIGURATION bit 0 ...

Страница 17: ...s when the required value is reached the display will end the editing mode after a time set in the EXIT_EDIT_TIME register object decimal address 223 An unavailable action is signalized by a double beep 4 6 2 Fan Control In order to change a fan mode on a touchscreen use small fan and big fan buttons Pressing either of the buttons changes the fan mode to one of the available off no icon on a fan c...

Страница 18: ...oftware User Manual www ismacontrolli com DMP253en 1st Issue rev 0 04 2022 page 18 of 49 4 6 4 CO2 Alarm If a CO2 alarm occurs it can be switched off by pressing any button on the touchscreen see CO2 Alarm ...

Страница 19: ...ature sensor is a standard equipment in the TP panel The temperature sensor s configuration data is available in the following parameters or in the iSMA Configurator TEMPERATURE_SENSOR indicates a current temperature value with offset Modbus register 30301 BACnet object AI4 property Present Value TEMPERATURE_SENSOR_OFFSET allows to set an offset value for the temperature sensor correction to the t...

Страница 20: ...lue with offset Modbus register 30303 BACnet object AI6 property Present Value CO2_OFFSET allows to set an offset value for the CO2 sensor correction to the CO2 sensor s value The default value is 0 Modbus register 40306 BACnet object AI6 property 4205 CO2_FILTER allows to set a filtering value for the CO2 sensor expressed in seconds The default value is 2 seconds Modbus register 40309 BACnet obje...

Страница 21: ...alue multiplied by 10 The default value is 180 18oC Modbus register 41505 BACnet object AV56 property Low Limit SETPOINT_HIGH_LIMIT allows to set a maximum temperature setpoint value which can be set by user The register contains a value multiplied by 10 The default value is 240 24oC Modbus register 41506 BACnet object AV56 property High Limit OFFSET_RANGE allows to set a limit for temperature off...

Страница 22: ...d to one decimal place The register contains a value multiplied by 10 The default value is 10 1oC Modbus register 41508 BACnet object AV56 property 4206 EXIT_EDIT_TIME allows to set the time after which edition of any editable parameter is finished The parameter is set in seconds The default value is set to 5 seconds Modbus register 40224 BACnet object AO17 property Present Value How to Change the...

Страница 23: ...erty Present Value The CO2 alarm can be configured using the following parameters CO2_SETPOINT_FOR_ALARM allows to set a tipping point for CO2 alarm The default value is set to 1500 ppm Modbus register 40226 BACnet object AO19 property Present Value CO2_HYSTERESIS_FOR_ALARM allows to set a hysteresis value for launching the CO2 alarm The default value is set to 100 ppm Modbus register 40227 BACnet...

Страница 24: ...witches on the function of LCD background illumination flashing when the CO2 alarm occurs If the bit 5 is true the CO2 alarm is indicated by the LCD display flashing Modbus register 40205 BACnet object BO5 property Present Value DEVICE_CONFIGURATION bit 6 CO2_ALARM_BUZZER switches a buzzer on when the CO2 alarm occurs If the bit 6 is true the CO2 alarm is indicated by the buzzer which emits sounds...

Страница 25: ...w Register Value Fan Mode Description 0 Off default Fan is off 1 Manual speed 1 Fan works in speed 1 manual mode 2 Manual speed 2 Fan works in speed 2 manual mode 3 Manual speed 3 Fan works in speed 3 manual mode 4 Auto speed 1 Fan works in speed 1 auto mode 5 Auto speed 2 Fan works in speed 2 auto mode 6 Auto speed 3 Fan works in speed 3 auto mode Table 15 The FAN_CURRENT_SPEED register values Mo...

Страница 26: ...ding on the configurations FAN_CONFIGURATION bit 1 EDITABLE enables or disables the fan to be edited locally from the panel Modbus register 41614 BACnet object MSV1 property 4200 FAN_CONFIGURATION bit 2 FAN_PART_EDITABLE allows to set the fan to be fully editable all modes stored in the FAN_MODE register available or partly editable selection between the auto mode and off Modbus register 41614 BAC...

Страница 27: ... the value by one Use a big fan button to increase the value by one Reached limit is signalized by a double beep A long press is not available for this feature 6 1 1 LEDs Value of the FAN_CURRENT_SPEED parameter is presented on the LEDs ladder as follows fan speeds from 1 to 3 lights up a single led for each level same for manual and auto auto settings light up an Auto LED ...

Страница 28: ...ancy Status 0 Unoccupied 1 Occupied 2 Standby 3 Forced occupied Table 18 Occupancy statuses Modbus register 41701 BACnet object MSV3 property Present Value This value can be updated in two ways depending on the OCCUPIED_CONFIG_LOCAL_MODE parameter OCCUPANCY_CONFIGURATION bit 6 OCCUPIED_CONFIG_LOCAL_MODE allows to set the occupancy to the local mode or BMS mode Local Mode the panel s occupancy sett...

Страница 29: ...to be edited locally from the panel Modbus register 41707 BACnet object MSV4 property 4200 How to Change the Occupancy on the Touchscreen Use a house button to toggle between occupied and unoccupied statuses A long press is not available for this feature 7 1 1 LEDs Value of the OCCUPANCY_CURRENT_STATUS parameter is presented on a house LEDs ladder as follows value 0 unoccupied in house LED is off ...

Страница 30: ... The ECO feature allows a user to light up an ECO LED on the TP panel useful for example if the TP panel is connected to a controller with an eco application ICON DISPLAY bit 8 ECO allows to activate or inactivate an ECO icon green LED Modbus register 40219 BACnet object BO22 property Present Value ...

Страница 31: ...l s version 11210 0x7016 Panel in bootloader 23910 0xEF16 Version Firmware version multiplied by 10 1010 0x0A16 means 1 0 firmware version Table 19 The VERSION_TYPE register values The VERSION_TYPE register also allows to enable 1 of 4 available actions reset panel reload settings reset settings enter bootloader If the register receives one of the following values it invokes a relevant action and ...

Страница 32: ...he panel s hardware version Modbus register 31303 BACnet object DEVICE property 3020 FLASH_BOOT_VERSION indicates the panel s bootloader version Modbus register 31304 BACnet object N A FW_VERSION indicates the panel s firmware version separated from the VERSION_TYPE register s value Modbus register 31305 BACnet object N A FLASH_SERIAL_NUMBER indicates the panel s serial number Modbus registers 313...

Страница 33: ...umber of received Modbus frames reset at the start of the panel and at the change of transmission parameters 30006 5 0x05 ERROR_FRAMES_CO UNTER Read only 0 The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters 30008 7 0x07 TRANSMITTED_FRA ME_COUNTER Read only 0 The number of transmitted Modbus frames reset at the start of the panel ...

Страница 34: ...xC8 BACKLIGHT_LCD Read only Actual display illumination value 30202 201 0xC9 BACKLIGHT_KEYPA D Read only Actual keypad illumination value 40205 204 0xCC DEVICE_CONFIGUR ATION Read write 105 Bit Name 0 1 0 BUZZER Not active Active def Activates inactivates a buzzer 3 BACKLIGHT_LCD Not active Active def Switches on off display s backlight 4 BACKLIGHT_KEYPA D Not active Active def Switches on off key...

Страница 35: ... active mode to idle expressed in seconds 40211 210 0xD2 BACKLIGHT_LCD_TI ME_TO_STANDBY Read write 5 Sets the time after which the LCD display goes from the idle mode to standby expressed in seconds 40212 211 0xD3 BACKLIGHT_KEYPA D_ACTIVE Read write 10 Contains a value of the keypad illumination in the active mode expressed in 40213 212 0xD4 BACKLIGHT_KEYPA D_IDLE Read write 40 Contains a value of...

Страница 36: ...5 ALARM_STATUS Read only CO2 current alarm status 30231 230 0xE6 NAVIGATIONAL_LE D_MODE Read write 1 0 4 Sets a mode of the navigational LED Bit Name 0 1 0 OFF Not active Active 1 ON default Not active Active 2 Active on IDLE and STANDBY Not active Active 3 Active on IDLE only Not active Active 4 Active on STANDBY only Not active Active 30232 231 0xE7 NAVIGATIONAL_LE D_BRIGHTNESS Read write 100 0 ...

Страница 37: ...set 40306 305 0x13 1 CO2_SENSOR_OFFS ET Read write 0 CO2 sensor offset 40307 306 0x13 2 TEMPERATURE_FILT ER Read write 60 Filtering time for the temperature sensor seconds 40308 307 0x13 3 HUMIDITY_FILTER Read write 60 Filtering time for the humidity sensor seconds 40309 308 0x13 4 CO2_FILTER Read write 60 Filtering time for the CO2 sensor seconds 40316 315 0x13 B TEMPERATURE_CO NFIGURATION Read w...

Страница 38: ..._VERSION Read only FW version separated from the VERSION_TYPE register 31305 1304 0x51 8 FLASH_SERIAL_NU MBER_1 Read only Serial number 31306 1305 0x51 9 FLASH_SERIAL_NU MBER_2 Read only Serial number 31307 1306 0x51 A FLASH_SERIAL_NU MBER_3 Read only Serial number 31308 1307 0x51 B FLASH_SERIAL_NU MBER_4 Read only Serial number 41501 1500 0x5D C SETPOINT_VALUE Read write 0 500 Temperature setpoin...

Страница 39: ...ature setpoint visibility on a display 1 EDITABLE Not editable Editable def Activates inactivates editing of a temperature setpoint locally on the panel 2 OPERATING_MODE Changing offset Changi ng setpoin t def Switches between changing offset or setpoint 3 SETPOINT_DISPLAY Show change offset Show change effectiv e setpoin t def Switches between changing offset or setpoint 4 THIRD_POINT_ACTI VE No ...

Страница 40: ... FAN_CONFIG_LOCA L_MODE BMS def Local Switches between BMS local modes 41701 1700 0x6A 4 OCCUPANCY_CURR ENT_STATUS Read write Occupancy status 41702 1701 0x6A 5 OCCUPANCY_MOD E Read write Occupancy mode 41707 1706 0x6A A OCCUPANCY_CONF IGURATION Read write 2 Bit Name 0 1 1 EDITABLE Not editable Editable def Switches on off editing occupancy statues locally 6 OCCUPIED_CONFIG _LOCAL_MODE BMS def Loc...

Страница 41: ...e start of the panel and at the change of transmission parameters Device 5103 5 0x05 ERROR_FRAME S_COUNTER Read only 0 The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters Device 5104 7 0x07 TRANSMITTED_ FRAME_COUN TER Read only 0 The number of transmitted Modbus frames reset at the start of the panel and at the change of transmiss...

Страница 42: ...illumination value 204 0xCC DEVICE_CONFI GURATION Read write BO0 Present Value BUZZER_ACTIV E 1 Activates 1 or deactivates 0 a buzzer BO3 Present Value LCD_BACKLIG HT_ACTIVE 1 Switches the LCD background illumination on 1 BO4 Present Value KEYPAD_BACK LIGHT_ACTIVE 1 Switches the keypad background illumination on 1 BO5 Present Value CO2_ALARM_L CD Switches on the function of LCD background illumina...

Страница 43: ...tive mode expressed in AO4 Present Value 207 0xCF BACKLIGHT_LC D_IDLE Read write 40 Contains a value of the LCD display illumination in the idle mode expressed in AO5 Present Value 208 0xD0 BACKLIGHT_LC D_STANDBY Read write 0 Contains a value of the LCD display illumination in the standby mode expressed in AO6 Present Value 209 0xD1 BACKLIGHT_LC D_TIME_TO_ID LE Read write 10 Sets the time after wh...

Страница 44: ...n the idle mode expressed in AO10 Present Value 213 0xD5 BACKLIGHT_KE YPAD_STANDB Y Read write 60 Contains a value of the keypad illumination in the standby mode expressed in AO11 Present Value 214 0xD6 BACKLIGHT_KE YPAD_TIME_TO _IDLE Read write 10 Sets the time after which the keypad goes from the active mode to idle expressed in seconds AO12 Present Value 215 0xD7 BACKLIGHT_KE YPAD_TIME_TO _STAN...

Страница 45: ...ATU S Read only CO2 current alarm status MSV5 Present Value 230 0xE6 NAVIGATIONA L_LED_MODE Read write 1 0 4 Sets a mode of the navigational LED AO22 Present Value 231 0xE7 NAVIGATIONA L_LED_BRIGHT NESS Read write 100 0 100 Navigational LED brightness AO23 Present Value 232 0xE8 NAVIGATIONA L_LED_RED Read write 100 0 100 Navigational LED color red component intensity AO24 Present Value 233 0xE9 NA...

Страница 46: ...et AI6 4205 305 0x13 1 CO2_SENSOR_ OFFSET Read write 0 CO2 sensor offset AI4 4003 306 0x13 2 TEMPERATURE _FILTER Read write 60 Filtering time for the temperature sensor seconds AI5 4003 307 0x13 3 HUMIDITY_FILT ER Read write 60 Filtering time for the humidity sensor seconds AI6 4003 308 0x13 4 CO2_FILTER Read write 60 Filtering time for the CO2 sensor seconds 315 0x13 B TEMPERATURE _CONFIGURATI ON...

Страница 47: ...d write 0 500 Temperature setpoint value AI 3 Present Value 1501 0x5D D EFFECTIVE_SET POINT Read only Sum of setpoint and offset values AV 57 Present Value 1502 0x5D E DEFAULT_SETP OINT Read write 210 0 500 Default temperature setpoint AV 58 Present Value 1503 0x5D F OFFSET_SETPO INT Read write 0 0 500 Temperature offset for setpoint AV 56 Low Limit 1504 0x5E 0 SETPOINT_LO W_LIMIT Read write 180 M...

Страница 48: ...sables editing of the temperature setpoint locally from the panel BO55 Present Value OPERATING_M ODE Sets the operating mode of the temperature setpoint configuration BO56 Present Value SETPOINT_DIS PLAY Configures the temperature setpoint display AV56 4202 THIRD_POINT_ ACTIVE Enables or disables decimal values in the temperature setpoint MSV0 Present Value 1600 0x64 0 FAN_CURRENT _SPEED Read writ...

Страница 49: ...e FAN_PART_EDI TABLE Configures editing of fan modes BO60 Present Value FAN_CONFIG_L OCAL_MODE Local BMS mode MSV3 Present Value 1700 0x6A 4 OCCUPANCY_C URRENT_STAT US Read write Occupancy status MSV4 Present Value 1701 0x6A 5 OCCUPANCY_ MODE Read write Occupancy mode 1706 0x6A A OCCUPANCY_C ONFIGURATIO N Read write 2 MSV4 4200 EDITABLE Activates or inactivated editing occupancy statutes locally i...

Отзывы: