67
capacity is changed.
Maximum
Charging
Current
--
Set battery maximum charging current (1~128A)
2A (Default)
MUST be set after UPS installation or Battery
capacity is changed.
Battery Low/
Shutdown
SETTING
Battery Low
Voltage
Set battery low voltage (10.5~11.5V)x(battery Number)
11V x Battery Number (Default)
Battery Low
Capacity
Set battery low capacity (20~50%)
20% (Default)
Battery Shutdown
Voltage
Set battery voltage point for system shutdown in battery
mode (10.0~11V) x (battery Number)
10V x Battery Number (Default)
BATTERY TEST
Periodic Battery
Test
Set periodic battery test disable or enable
Disable (Default)
Enable
Battery Test
Interval
Set battery test interval (7~99 Days)
30 Days (Default)
Stop by Time
Set testing time for battery test (10~1000sec)
10 sec (Default)
Stop by Battery
Voltage
Set stop battery voltage in battery test (11~12V) x
(battery Number)
11V x Battery Number (Default)
Stop by Battery
Capacity
Set battery capacity to stop battery-testing. (20~50%)
20% (Default)
Battery Age
Alert
Battery Age Alert
(Months)
Set battery age for replacement. (Disable,12~60Months)
Disable (Default)
If this feature is enabled and the battery has been
installed over this period, there is a warning “Battery Age
Alert” to indicate it.
Temperature
Compensation
--
Set battery temperature compensation. (0~-5 (mV/
℃
/cl))
0(mV/
℃
/cl) (Default)
Charging
Voltage
--
Set battery charging voltage. (2.30~2.35V)
2.35V (Default)
Set battery float voltage. (2.23~2.35V)
2.29V (Default)