84
Fault! DSP MCU Stop
Communicate
As stated.
Contact service personnel.
Fault! Bypass Temperature
Fault
As stated
Check if the ambient temperature is over
specification.
Or contact service personnel.
Fault! Bypass SCR Fault
As stated.
Contact service personnel.
Warning! EPO Active
Check the EPO connector
Check if the connector is loose when EPO
acts abnormally.
Warning! Over Load Fail
The load devices are demanding more
power than the UPS can supply. Line
mode will transfer to Bypass mode.
Reduce some load and check output
Load-Capacity and specification
Warning! Communicate CAN
Fail
CAN communication error
Contact service personnel.
Warning! Over Load
In Line mode, the load devices are
demanding more power than the UPS
can supply.
Reduce some load and check output
Load-Capacity and specification
Warning! Battery Open
Battery not connected
1.
Check battery breaker.
2.
Check if the battery connection is
well connected.
3.
Check the setting of Nominal Battery
voltage.
4.
Contact service personnel if
necessary
Warning! Battery voltage
High
Battery voltage is too High
Check the setting of Nominal Battery
voltage and contact service personnel.
Warning! Module Un-Lock
As stated.
Check if module is locked well.
Warning! Turn On Abnormal As stated.
Check if the input voltage or frequency is
out of range.
Warning! Charge Fail
As stated.
Contact service personnel.
Warning! EEPROM Fail
EEPROM operation error
Contact service personnel.
Warning! Fan Lock
As stated.
Check if the fan is blocked or contact
service personnel.
Warning! Line Phase Error
As stated.
Check if the Mains phase sequence is
correct and contact service personnel.
Warning! Bypass Phase
Error
As stated.
Check if the Bypass phase sequence is
correct and contact service personnel.
Warning! N Loss
Neutral loss
Check if the Neutral connection is well
and contact service personnel..
Warning! Internal Initial Fail As stated.
Contact service personnel.
Warning! Comm. Syn. Signal
Fail
Communicate Synchronization Signal
Fail
Contact service personnel.
Warning! Comm. TRIG0 Fail Communicate Trigger signal fault
Contact service personnel.
Warning! Redundancy Set
Fail
As stated.
Check the redundancy setting is correct
and contact service personnel.
Warning! Parallel Sys
Config. Wrong
Parallel System Configure error
Contact service personnel.
Warning! Maintenance
Bypass
Enter maintenance
Check if the connector is loose when it
acts abnormally.
Warning! Battery Age Alert
Battery Life expiration
Check if the battery has been used over
its service age. Or contact service