2. Installation
2.1 Initial Inspection
1.
Visually examine if there is any damage inside and outside of packages in the process of the
transportation. If any damage, report it to the carrier immediately.
2.
Verify the product label and confirm the consistency of the equipment.
3.
If the equipment needs to be returned, carefully repack the equipment by using the originally
packing material that came with.
2.2 Installation Environment
1.
The UPS is designed for indoor use only and should be located in a clean environment with
adequate ventilation to keep the environmental parameters within the required specification.
2.
Make sure that transportation routes (e.g. corridor, door gate, elevator, etc.) and installation
area can accommodate and bear the weight of the UPS, the external battery cabinet and
handling equipment.
3.
The UPS uses forced convection cooling by internal fans. Cooling air enters the module
through ventilation grills located at the front of the cabinet and exhausted through grills
located in the rear part of the cabinet. Please do not block the ventilation holes.
4.
Ensure that the installation area is spacious for maintenance and ventilation.
5.
Keep the temperature of installation area around 30°C and humidity within 90%. The highest
operating altitude is 1000 meters above sea level.
6.
If necessary, install a system of room extractor fans to avoid formation of room temperature.
Air filters are necessary if the UPS is operated in a dusty environment.
7.
It is recommended that you parallel the external battery cabinets to the UPS. The following
instructions of clearances are suggested:
Keep a clearance of 100cm from the top of the UPS for maintenance, wiring and
ventilation.
Keep a clearance of 100cm from the back of the UPS and the external battery cabinets for
ventilation.
Keep a clearance of 150cm from the front of the UPS and the external battery cabinets
for maintenance and ventilation.
8.
For safety concerns, we suggest that you shall:
Equip with CO2 or dry powder fire extinguishers near the installation area.
Install the UPS in an area where the walls, floors and ceilings were constructed by
fireproof materials.
9.
Do not allow unauthorized personnel to enter the installation area. Assign specific personnel
to keep the UPS key.