44
Step 5:
Then, UPS will enter Battery Mode as shown in the diagram below.
Step 6:
Switch ON the output breaker (Q3). Cold start startup procedure is complete.
3.3.3 Maintenance Bypass Operation
Follow the instruction to transfer to Maintenance Bypass and UPS protection as below.
3.3.3.1 Transfer to maintenance bypass
90KVA~210KVA.
300KVA
Step 1
:
Remove the mechanical lock plate of
Maintenance Bypass Breaker.
Remove the mechanical lock plate of
Maintenance Bypass Switch.
Step 2
Make sure the UPS operates in Bypass
mode as shown below.
Make sure the UPS operates in Bypass
mode as shown below.