Goodrive200A
inverters Function parameters
73
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
factory value changes with voltage level.
The setting range:200.0~2000.0V
In order to prevent customers set the value is too
large, it is recommended setting range:
voltage
380V
500V
660
range
685~750V
860~950V 1080~1180V
700.0V
500V
voltage:
900.0V
660V
voltage:
1120.0V
P08.39
Cooling fan
running
mode
Set the operation mode of the cooling fan.
0: Normal mode, after the rectifier receives
operation command or the detected temperature
of module is above 45
℃
or the module current is
above 20% of the rated current, the fan rotates.
1:The fan keeps on running after power on
(generally for the site with high temperature and
humidity)
0
○
P08.40
PWM
selection
0x00~0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1:Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
00
◎
P08.41
Over
commission
selection
0x00~0x11
LED ones
0: Invalid
1: Valid
LED tens
0: Light overcommission
1: Heavy overcommission
0x01
◎
P08.42
Keypad data
control
0x000~0x1223
LED ones:frequency enable selection
0:Both
∧
/
∨
keys and digital potentiometer
adjustments are valid
1:Only
∧
/
∨
keys adjustment is valid
0x0000
○
Содержание Goodrive 200A
Страница 1: ...Goodrive 200A Inverter ...
Страница 114: ...Goodrive200A inverters Fault tracking 109 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 115: ...Goodrive200A inverters Fault tracking 110 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 116: ...Goodrive200A inverters Fault tracking 111 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 162: ...6 6 0 0 1 0 0 3 4 2 201507 V1 2 ...