Goodrive200A
inverters Function parameters
49
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
adjusts the output voltage to save energy
P04.27
Voltage
setting
channel
Select the output setting channel at V/F curve
separation.
0: Keypad setting voltage: the output voltage is
determined by P04.28.
1:AI1 setting voltage(The inverter(
≤
15kW) can
be set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
which is 18.5kW or higer than 18.5kW)
2:AI2 setting voltage;
3:AI3 setting voltage;
4:HDI setting voltage;
5:Multi-step speed setting voltage;
6:PID setting voltage;
7:MODBUS communication setting voltage;
Note:
100% corresponds to the rated voltage of
the motor.
0
○
P04.28
Keypad
setting
voltage
The function code is the voltage digital set value
when the voltage setting channel is selected as
“keypad selection”
The setting range:0.0%~100.0%
100.0%
○
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the
inverter accelerates from the output minimum
voltage to the output maximum voltage.
Voltage decreasing time is the time when the
inverter decelerates from the output maximum
voltage to the output minimum voltage.
The setting range:0.0~3600.0s
5.0s
○
P04.30
Voltage
decreasing
time
5.0s
○
P04.31
Maximum
output
voltage
Set the upper and low limit of the output voltage.
The setting range of P04.31:P04.32~100.0%
(the rated voltage of the motor)
The setting range of P04.32:0.0%~ P04.31
(the rated voltage of the motor)
100.0%
◎
P04.32
Minimum
output
voltage
0.0%
◎
Содержание Goodrive 200A
Страница 1: ...Goodrive 200A Inverter ...
Страница 114: ...Goodrive200A inverters Fault tracking 109 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 115: ...Goodrive200A inverters Fault tracking 110 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 116: ...Goodrive200A inverters Fault tracking 111 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 162: ...6 6 0 0 1 0 0 3 4 2 201507 V1 2 ...