Goodrive200A
inverters Function parameters
83
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
corresponding function codes.
Setting range: 0x0000~0xFFFF
P10.36 PLC restart
0: Restart from the first step; stop during running
(cause by the stop command, fault or power
loss), run from the first step after restart.
1: Continue to run from the stop frequency; stop
during running(cause by stop command and
fault), the inverter will record the running time
automatically, enter into the step after restart and
keep the remaining running at the setting
frequency.
0
◎
P10.37
Multi-step
time unit
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is
counted by minute
0
◎
P11 Group Protective parameters
P11.00
Phase loss
protection
0x00~0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED hundreds:
0: Input phase loss hardware protection disable
1: Input phase loss hardware protection enable
111
○
P11.01
Sudden
power loss
frequency-de
creasing
0: Enable
1: Disable
0
○
P11.02
Frequency
decreasing
ratio of
sudden
power loss
Setting range: 0.00Hz/s~P00.03
(the Max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the inverter begin to decrease the running
frequency at P11.02, to make the inverter
generate power again. The returning power can
maintain the bus voltage to ensure a rated
running of the inverter until the recovery of
power.
Voltage degree
220V
380V
660V
10.00
Hz/s
○
Содержание Goodrive 200A
Страница 1: ...Goodrive 200A Inverter ...
Страница 114: ...Goodrive200A inverters Fault tracking 109 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 115: ...Goodrive200A inverters Fault tracking 110 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 116: ...Goodrive200A inverters Fault tracking 111 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 162: ...6 6 0 0 1 0 0 3 4 2 201507 V1 2 ...