Goodrive200A
inverters Function parameters
35
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
cancel the impact on the output voltage of the
inverter because of the bus voltage fluctuation.
P00.17 Inverter type
0:G type, for the constant torque load of rated
parameters
1:P type; for the variable torque load of rated
parameters (fans and water pumps)
GD200A series inverters can use G/P type, the
available motor power of G type is small one
power file than that of P type.
0
◎
P00.18
Function
restore
parameter
0:No operation
1:Restore the default value
2:Clear fault records
Note:
The function code will restore to 0 after
finishing the operation of the selected function
code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0
◎
P01 Group Start-up and stop control
P01.00 Start mode
0:Start-up directly:start from the starting
frequency P01.01
1:Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Start-up after speed tracking: start the rotating
motor smoothly after tracking the rotation speed
and direction automatically. It is suitable in the
cases where reverse rotation may occur to the
big inertia load during starting.
Note: This function is available for the inverters of
4kW and above.
0
◎
P01.01
Starting
frequency of
direct start
Starting frequency of direct start-up means the
original frequency during the inverter starting.
See P01.02 for detailed information.
Setting range: 0.00~50.00Hz
0.50Hz
◎
P01.02
Retention
time of the
starting
frequency
Set a proper starting frequency to increase the
torque of the inverter during starting. During the
retention time of the starting frequency, the
output frequency of the inverter is the starting
0.0s
◎
Содержание Goodrive 200A
Страница 1: ...Goodrive 200A Inverter ...
Страница 114: ...Goodrive200A inverters Fault tracking 109 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 115: ...Goodrive200A inverters Fault tracking 110 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 116: ...Goodrive200A inverters Fault tracking 111 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 162: ...6 6 0 0 1 0 0 3 4 2 201507 V1 2 ...