Goodrive200A
inverters Function parameters
62
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
valid in the keypad commands channels.
4: Clear UP/DOWN settings. Press QUICK/JOG
to clear the set value of UP/DOWN.
5: Coast to stop. Press QUICK/JOG to coast to
stop.
6: Shift the running commands source. Press
QUICK/JOG to shift the running commands
source.
7:Quick commission mode(committee according
to the non-factory parameter)
Note:
Press QUICK/JOGto shift between
forward rotation and reverse rotation, the inverter
does not record the state after shifting during
powering off. The inverter will run according to
parameter P00.13 during next powering on.
P07.03
Shifting
sequence
selection of
QUICK/JOG
commands
When P07.02=6, set the shifting sequence of
running command channels.
0:Keypad control→terminals control
→communication control
1:Keypad control←→terminals control
2:Keypad control←→communication control
3:Terminals control←→communication control
0
○
P07.04
STOP/RST
stop function
STOP/RST is valid for stop function. STOP/RST
is valid in any state for the fault reset.
0:Only valid for the keypad control
1:Both valid for keypad and terminals control
2:Both valid for keypad and communication
control
3:Valid for all control modes
0
○
P07.05
Parameters
state 1
0x0000~0xFFFF
BIT0:running frequency (Hz on)
BIT1:set frequency(Hz flickering)
BIT2:bus voltage (Hz on)
BIT3:output voltage(V on)
BIT4:output current(A on)
BIT5:running rotation speed (rpm on)
BIT6:output power(% on)
BIT7:output torque(% on)
BIT8:PID reference(% flickering)
BIT9:PID feedback value(% on)
BIT10:input terminals state
0x03FF
○
Содержание Goodrive 200A
Страница 1: ...Goodrive 200A Inverter ...
Страница 114: ...Goodrive200A inverters Fault tracking 109 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 115: ...Goodrive200A inverters Fault tracking 110 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 116: ...Goodrive200A inverters Fault tracking 111 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 162: ...6 6 0 0 1 0 0 3 4 2 201507 V1 2 ...