Goodrive200A
inverters Appendix C
147
connecting to the drive.
Note: Check the insulation of the input power cables according to local regulations
before connecting the cables.
Note:
1. It is appropriate to use the recommended cable size under 40
℃
and rated current. The
wiring distance should be no more than 100m.
2. Terminals P1, (+), PB and (-) connects the DC reactor options and parts.
The inverter
Recommended cable size(mm
2
)
Screw
R,S,T
U,V,W
PE
P1(+)
PB(+)(-)
Terminal
screw
size
Tightening
torque
(Nm)
GD200A -0R7G-4
2.5
2.5
2.5
2.5
M4
1.2~1.5
GD200A -1R5G-4
2.5
2.5
2.5
2.5
M4
1.2~1.5
GD200A -2R2G-4
2.5
2.5
2.5
2.5
M4
1.2~1.5
GD200A
-004G/5R5P-4
2.5
2.5
2.5
2.5
M4
1.2~1.5
GD200A
-5R5G/7R5P-4
4
4
2.5
2.5
M5
2~2.5
GD200A -7R5G/011P-4
6
6
4
2.5
M5
2~2.5
GD200A -011G/015P-4
10
10
6
4
M5
2~2.5
GD200A -015G/018P-4
10
10
10
4
M5
2~2.5
GD200A -018G/022P-4
16
16
10
6
M6
4~6
GD200A -022G/030P-4
25
16
16
10
M6
4~6
GD200A -030G/037P-4
25
16
16
10
M8
9~11
GD200A -037G/045P-4
35
16
25
16
M8
9~11
GD200A -045G/055P-4
50
25
35
25
M8
9~11
GD200A -055G/075P-4
70
35
50
25
M10
18~23
GD200A -075G/090P-4
95
50
70
35
M10
18~23
GD200A -090G/110P-4
120
70
95
35
M10
18~23
GD200A -110G/132P-4
150
70
120
70
M12
31~40
GD200A -132G/160P-4
185
95
150
95
M12
31~40
GD200A -160G/185P-4
240
95
185
50
M12
31~40
GD200A -185G/200P-4
120*2P
150
95*2P
50
M12
31~40
GD200A -200G/220P-4
120*2P
150
95*2P
50
M12
31~40
GD200A -220G/250P-4
150*2P
150
95*2P
50
M12
31~40
GD200A -250G/280P-4
150*2P
150
120*2P
95
M12
31~40
GD200A -280G/315P-4
185*2P
185
120*2P
95
M12
31~40
GD200A -315G/350P-4
185*2P
185
120*2P
95
M12
31~40
GD200A -350G/400P-4
95*4P
95*2P
150*2P
120
M12
31~40
GD200A -400G-4
95*4P
95*2P
150*2P
120
M12
31~40
GD200A -500G-4
120*4P
95*2P
95*4P
120
M12
31~40
Содержание Goodrive 200A
Страница 1: ...Goodrive 200A Inverter ...
Страница 114: ...Goodrive200A inverters Fault tracking 109 8 6 2 Motor vibration 8 6 3 Overvoltage ...
Страница 115: ...Goodrive200A inverters Fault tracking 110 8 6 4 Undervoltage fault 8 6 5 Abnormal motor heat ...
Страница 116: ...Goodrive200A inverters Fault tracking 111 8 6 6 Inverter overheating 8 6 7 Stall during the acceleration of the motor ...
Страница 162: ...6 6 0 0 1 0 0 3 4 2 201507 V1 2 ...