Chapter 2: Installation
FlexZone™ Product Guide
47
Figure 54: FlexZone processor wiring diagram
Silver Network wiring connections
Note:
A network interface card is required to enable Silver Network
communications between a FlexZone processor and the Silver Network
manager.
Note:
For groups of FlexZone processors that communicate over the sensor
cables, only the processor that is connected directly to the Silver Network
requires an NIC.
Silver Network specifications
• Data rate - fixed 57.6 k bps
• Maximum 60 devices spread over up to 4 independent network loops
• Two communication Channels (Side A, Side B)
• Response time - 1 second, or less from alarm source to Network Manager
(per loop)
• Network termination - not required
• Transmission media/maximum separation distances between processors:
• EIA-422 copper wire - 1.2 km (0.75 mi.) - 2 pairs per Channel
• Multi-mode fiber optic cable (820 nm) - 2.2 km (1.4 mi.) - 2 fibers per
Channel - optical power budget 8 dB
T7
T4
T8
-
+
T9
AUX 1
- +
AUX 2
- +
RELAY 1
NC COM NO
RELAY 2
NC COM NO
RELAY 3
NC COM NO
RELAY 4
NC COM NO
A-SIDE
B-SIDE
POWER
-
+
-
-
+
-
T7
T4
sensor cable
T8
T9
relay outputs
self-test/auxiliary
inputs
power
input
A-Side
B-Side
- DC GND
+ 12 to 48 VDC
auxiliary/self-test inputs
-
+
AUX input 1
-
+
AUX input 2
relay 1 NC
relay 1 COM
relay 1 NO
relay 2 NC
relay 2 COM
relay 2 NO
relay 4 NO
relay 4 COM
relay 4 NC
relay 3 NO
relay 3 COM
relay 3 NC
+ center conductor
- shield
B SIDE sensor cable
+ center conductor
- shield
A SIDE sensor cable
- shield
- shield
T4 power output for
processors receiving
power over sensor
cables
Содержание FlexZone Series
Страница 1: ...FlexZone Product Guide P N 466 2877 REV C ISS 19MAR19...
Страница 6: ......
Страница 23: ...Chapter 1 System planning FlexZone Product Guide 17 Figure 11 High security redundancy 2 1 km example...
Страница 24: ......
Страница 41: ...Chapter 2 Installation FlexZone Product Guide 35 Figure 40 Mounting the splice enclosure 15 cm...
Страница 61: ...Chapter 2 Installation FlexZone Product Guide 55 Figure 63 UltraWave connection diagrams Silver Network Relay...
Страница 62: ......
Страница 86: ......
Страница 94: ......