TS25 MKII : TS25-BAS1-KIT : TS25-BAS1-CAN-240
Battery charger/analyser : Operators Manual
immediately and the display will show
END
and the
END
led will remain
illuminated.
The display will remain in this state until either
MUTE
of
STOP
is pressed.
4.3.6 CHARGE PROCESS AUTO TERMINATE
If constant voltage charging the process will automatically stop when the test
time has been completed.
If constant current charging is programmed then the charge will terminate on the
full charge time completed or if the battery terminal voltage reached the voltage
set point.
If constant current with additional time mode is being performed then the unit
will stop when the additional time has been used or if the voltage set point is not
reached within 24 hours of the charge starting.
In all cases the charge process will terminate immediately, the audible alarm will
sound and the
ALARM
and
END
lights will illuminate and the display will show the
reason for terminating the process.
To clear the alarm the
MUTE
or
STOP
key must be pressed.
Process termination codes:
E 1
The process time or additional time is complete.
E 3
Voltage set point reached (Constant Current Mode Only).
E 4
The voltage set point has not been reached within 24Hours.