4 USING THE TS25 MKII
4.1 CONNECTING BATTERIES
For all methods of use of the battery charger the battery to be tested or charged must
only be connected when the charger is either:
SWITCHED OFF
or
SWITCHED ON AND
END
LAMP ILLUMINATED
Connecting a battery while the charge is operational would damage the equipment,
and possible draw an electrical arc that, may cause an explosion from the venting
gases being emitted from the battery.
Care must also be executed in ensuring that the bared ends of the battery leads do
not come in contact with the metalwork of the charger as this may also cause
electrical arcing and or explosion risk.
WARNING
THE BATTERY SHOULD NEVER BE CONNECTED OR DISCONNECTED FROM THE
UNIT WHEN A CHARGE OR TEST IS IN PROGRESS AS ARCING CAN OCCUR
CAUSING AN EXPLOSION FROM GASSES VENTING FROM BATTERIES BEING
PROCESSED
THE BATTERY SHOULD ALWAYS BE ISOLATED FROM ANY EQUIPMENT
BEFORE BEING CONNECTED
Stray ground loops between the attached equipment and the TS25 MKII could cause
catastrophic damage to the unit and the attached equipment.
The battery or batteries must be connected to the TS25 MKII as shown in the
following diagram: -