- 58 -
Parameter Table
Parameter
Parameter Name
Setting Range
Unit Default Commission
F4-08
PTC function enable
(On-board expansion
card)
37: Command source switchover
terminal 2
38: PID integral pause
39: Switchover between main
frequency source X and
preset frequency
40: Switchover between auxiliary
frequency source Y and
preset frequency
41: Motor selection terminal 1
42: Motor selection terminal 2
43: PID parameter switchover
44: User defined fault 1
45: User defined fault 2
46: Speed control/Torque control
switchover
47: Emergency stop
48: External STOP terminal 2
49: Deceleration DC braking
50: Clear the current running
time
51: Switchover between two-line
mode and three-line mode
52 to 59: Reserved
-
F4-10
DI filter time
0.000 to 1.000
s
0.010
-
F4-11
Terminal command
mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
N.A
0
-
F4-12
Terminal UP/DOWN rate
0.01 to 65.535
Hz/
s
1.00
-
F4-13
AI curve 1 minimum
input
0.00 to F4-15
V
0.00
-
F4-14
Corresponding setting
of AI curve 1 minimum
input
-100.00 to 100.00
%
0.0
-
F4-15
AI curve 1 maximum
input
F4-13 to 10.00V
V
5.00
-
F4-16
Corresponding setting
of AI curve 1 maximum
input
-100.00 to 100.00
%
100.0
-
F4-17
AI1 filter time
0.00 to 10.00
s
0.10
-