background image

 

- 43 -

Trouble shooting and Solutions

5 

Trouble shooting and Solutions

5.1  Fault Codes and Solutions

Troubleshoot the faults occurred during operating the AC drive as follows.

Display

Fault Name

Possible Causes

Solutions

Err02

Overcurrent 

during 

acceleration

1. The output circuit is short circuited.

2. The acceleration time is too short.

3. Manual torque boost or V/F curve is 

not appropriate.

4. The power supply is too low.

5. The startup operation is performed 

on the rotating motor.

6. A sudden load is added during 

acceleration.

7. The AC drive model is of too small 

power class.

1. Eliminate short circuit.

2. Increase the acceleration time 

F0-17.

3.Adjust the manual torque boost 

or V/F curve.

4. Check that the power supply is 

normal.

5. Select speed tracking restart or 

start the motor after it stops.

6. Remove the added load.

7. Select a drive of higher power 

class.

Err03

Overcurrent 

during 

deceleration

1. The output circuit is short circuited.

2. The deceleration time is too short.

3. The power supply is too low.

4. A sudden load is added during 

deceleration.

5. The braking resistor is not installed.

1. Eliminate short circuit.

2. Increase the deceleration 

timeF0-18.

3. Check the power supply, and 

ensure it is normal.

4. Remove the added load.

5. Install the braking resistor.

Err04 Overcurrent at 

constant speed

1. The output circuit is short circuited.

2. The power supply is too low.

3. A sudden load is added during 

operation.

4. The AC drive model is of too small 

power class.

1. Eliminate short circuit.

2. Adjust power supply to normal 

range.

3. Remove the added load.

4. Select a drive of higher power 

class.

Err05

Overvoltage 

during 

acceleration

1. The DC bus voltage is too high

.

2. An external force drives the motor 

during acceleration.

3. The acceleration time is too short.

4. The braking resistor is not installed.

1. Replace with a proper braking 

resistor.

2. Cancel the external force or 

install braking resistor.

3. Increase the acceleration time.

4. Install a braking resistor.

Err06

Overvoltage 

during 

deceleration

1. The DC bus voltage is too high

.

2. An external force drives the motor 

during deceleration.

3. The deceleration time is too short.

4. The braking resistor is not installed.

1. Replace with a proper braking 

resistor.

2. Cancel the external force or 

install braking resistor.

3. Increase the deceleration time.

4. Install the braking resistor.

Содержание Aonarch MD500L Series

Страница 1: ...0 6HULHV ULYH 8VHU XLGH QGXVWULDO XWRPDWLRQ QWHOOLJHQW OHYDWRU 1HZ QHUJ 9HKLFOH QGXVWULDO 5RERW 5DLO 7UDQVLW DWD FRGH...

Страница 2: ...fine tuning to optimize the operation performance can be undertaken Such parameter tuning should be done by qualified personnel who have prior training on AC Drives Some parameter settings can have ad...

Страница 3: ...Revision History 2 Revision History Date Version Revision Description July 2021 A00 First release...

Страница 4: ...ponsibility for any personal injuries or property damage caused by improper usage Safety Levels and Definitions DANGER indicates that failure to comply with the notice will result in severe personal i...

Страница 5: ...uipment with other equipment or materials that may harm or have negative impacts on this equipment WARNING Use professional loading and unloading equipment to carry large scale or heavy equipment When...

Страница 6: ...ocedures and wear an antistatic wrist strap Failure to comply will result in damage to internal equipment circuits WARNING Never connect the power cable to output terminals of the equipment Failure to...

Страница 7: ...n the equipment at power on Failure to comply will result in an electric shock Before maintenance cut off all equipment power supplies and wait at least 10 minutes WARNING Perform daily and periodic i...

Страница 8: ...t nameplate indicate compliance with the corresponding certificates and standards Certification Mark Directives Standard CE EMC directive 2014 30 EU EN 61800 3 LVD directive 2014 35 EU EN 61800 5 1 Ro...

Страница 9: ...l wiring 1 use multi reference input as frequency reference 16 2 2 2 Typical wiring 2 use analog input as frequency reference 17 2 2 3 Main Circuit Terminals 18 2 2 4 Control Circuit Terminals 19 2 2...

Страница 10: ...2 Replacing Cooling Fans 50 6 4 Storage 52 7 Parameter Table 53 Group F0 fundamental 53 Group F1 motor 1 parameters 54 Group F2 vector control 55 Group F3 V F control 55 Group F4 input terminals 57 Gr...

Страница 11: ...namic Braking Unit B Built in Code Drive Duty G Heavy Duty Code Power Rating 3 7 3 7 kW 5 5 5 5 kW 7 5 7 5 kW 11 11 kW 15 15 kW 18 5 18 5 kW 22 22 kW 30 30 kW Code Voltage Class T Three phase 380 480...

Страница 12: ...1 1 Description of components No Component No Component Front cover Main circuit terminals Barcode Grounding terminals Operating panel Fan cover Fixing pin of extension encoder card Cooling fan Fixing...

Страница 13: ...aracteristics Overload capacity 150 for 60s 180 for 3s Input Rated input current A 11 4 16 7 21 9 32 2 41 3 49 5 59 57 Rated voltage frequency AC Three phase 380 to 480 V 50 60 Hz Allowed voltage fluc...

Страница 14: ...ns of MD500L Model Hole Dimensions mm Overall Dimensions mm Hole Diameter mm Weight kg A B H W D d MD500L T3 7GBO 119 189 200 130 162 5 2 0 MD500L T5 5GBO MD500L T7 5GBO 128 238 250 140 170 6 3 3 MD50...

Страница 15: ...affected by levels of vibration that exceeds 0 6 g Keep the AC drive away from punch machines 4 Ensure that the mounting location is away from direct sunlight damp or water drops 5 Ensure that the mo...

Страница 16: ...ounting Figure 2 2 Backplate mounting of MD500L NOTE In this mode do not just secure two screws on the top of the AC drive otherwise the AC drive may fall off or be damaged due to the unbalanced effec...

Страница 17: ...MD500L Gearbox 110V DC Safety circuit Safety circuit Drive ready Analog input 1 0 10V Analog input 2 0 10V 0 20mA Brake Relay IGBT Enable UPS Enable Single phase UPS select MC Relay Phase Monitor Rel...

Страница 18: ...capacity IM MD500L Gearbox 110V DC Safety circuit Safety circuit Drive ready Analog input 1 0 10V Analog input 2 0 10V 0 20mA Brake Relay IGBT Enable UPS Enable Single phase UPS select MC Relay Phase...

Страница 19: ...nals Terminal Name Description R S T Three phase power supply input terminals Connected to AC input three phase power supply DC bus positive and negative terminals Common DC bus input connected to the...

Страница 20: ...e 2 7 Control circuit terminal arrangement Table 2 2 Description of control circuit terminals Type Terminal Mark Terminal Name Description Power supply 10 V GND 10 V power supply Provides 10 V power s...

Страница 21: ...speed pulse inputs Maximum input frequency 100 kHz Input impedance 1 03 k Analog output AO1 GND Analog output 1 Either a voltage or current output determined by jumper J7 Output voltage range 0 to 10...

Страница 22: ...2 input selection Either a voltage or a current input Voltage input by default J10 AI2 input impedance selection Either 500 or 250 input 500 input by default NOTE 1 When the ambient environment is abo...

Страница 23: ...s Terminal Pin Function Description J3 BK BK MC MC BK Relay output terminal Brake Relay BK MC Relay output terminal MC Relay MC J4 485 485 PT CGND 485 RS485 communication input terminal 485 PT Tempera...

Страница 24: ...ication protocol termination resistor selection Left The bus termination resistor available Right The bus termination resistor not available J2 Temperature detection selection Left PTC Right PT100 J3...

Страница 25: ...5 8 3 7 56 5 PNNBOE TPVSDF JOEJDBUPS 3VOOJOH TUBUVT JOEJDBUPS EJTQMBZ GPS QBSBNFUFST 1SPHSBN LFZ FOV NPEF TFMFDUJPO LFZ 3VO LFZ 3VOOJOH EJSFDUJPO JOEJDBUPS VUP UVOJOH 5PSRVF DPOUSPM BVMU JOEJDBUPS 6OJ...

Страница 26: ...n Perform a function switchover as defined by the setting of F7 01 MF K key function selection QUICK Menu mode selection Switch over between menu modes as defined by the setting of FP 03 Selection of...

Страница 27: ...que control and fault indicators TUNE TC OFF indicates that the AC drive is normal TUNE TC ON indicates the torque control mode TUNE TC FLASHING SLOWLY once a second indicates auto tuning status TUNE...

Страница 28: ...BOE SBLF POUBDUPS SBLF 3FMFBTF SFRVFODZ 5ISFTIPME OKFDUJPO GSFRVFODZ UISFTIPME SBLF QQMZ SFRVFODZ T 0QUJNJ F 4UBSU SFFQJOH POUBDUPS FMBZ 0 4FU 5JNF T OKFDUJPO BDUJWF TFU UJNF T OKFDUJPO FWFM OKFDUJPO...

Страница 29: ...rake contactor is energized Optimize profile generator active Motor start to run F8 57 F6 03 F6 04 RUN t6 DC injection 1 disable after the desired set time has elapsed F6 06 RUN t7 Start optimizer pro...

Страница 30: ...5s Start frequency is too low Increase F6 03 ranging 0 to1 5Hz Torque output is insufficient Make sure F3 00 0 F3 01 0 Starting jerk Brake device releases too late Decrease F8 57 ranging 0 to 0 5s St...

Страница 31: ...current loop PI gains Double check the motor parameters and then perform motor auto tuning once more SFRVFODZ FNBOE 5JNF 4UBSU DDFMFSBUJPO PNJOBM TQFFE FDFMFSBUJPO SFFQJOH TQFFE 4UPQ Figure 4 3 MD500L...

Страница 32: ...o 20s then set F8 26 creeping speed Braking device applies too early Make sure F8 58 0 5Hz then increase F8 59 ranging 0 to 0 5s Too strong DC injection at stop Decrease F6 13 ranging 0 to 100 Slip To...

Страница 33: ...necessary steps for quick setup So it s seriously recommended to remove DI wirings at the beginning of commissioning Restore parameters FP 01 Parameter operation 0 1 0 No operation 1 Restore default s...

Страница 34: ...or 2 Set F1 37 3 and press ENTER the LEDs on the operating panel will display TUNE 3 Press the key RUN on the panel then the motor starts auto tuning It usually takes about 30 seconds to finish this a...

Страница 35: ...ting of AI1 maximum input 100 0 100 0 to 100 0 Set multi reference values FC 01 Reference 1 100 0 100 00 0 0 to 100 0 NOTE FC 01 is set as nominal speed of elevator FC 02 Reference 2 11 0 11 0 0 0 to...

Страница 36: ...reference then DI3 is useless just leave it alone If multi reference is used as frequency reference then signal nominal speed comes from elevator controller F4 03 DI4 function selection 13 13 Setting...

Страница 37: ...e as FM NOTE This signal goes to brake contactor Set magnetic contactor F8 60 Drive run delay ON set time 0 20 0 20 0 20 to 10 00s NOTE If MC is controlled by elevator controller then F8 60 is useless...

Страница 38: ...ation 3 S curve acceleration deceleration C F6 08 Time proportion of S curve at Accel start 80 0 80 0 0 0 to Min 100 0 F6 09 80 F6 09 Time proportion of S curve at Accel end 10 0 10 0 0 0 to Min 100 0...

Страница 39: ...F 1 Multi point V F Setting range 0 to 11 F3 01 Torque boost 0 0 0 0 0 0 to 30 0 NOTE If it is 0 then auto torque boost is activated and it is recommended to use auto torque boost Set SVC parameters F...

Страница 40: ...g circuits before opening the Output Contactor milliseconds later The AC drive IGBT firing can be electronically switched off with the IGBT Enable function as shown in the timing charts below CAUTION...

Страница 41: ...mmission F4 00 DI1 function selection 0 No function 1 Forward RUN FWD 2 Reverse RUN REV 8 IGBT Enable 12 Multi reference terminal 1 13 Multi reference terminal 2 14 Multi reference terminal 3 15 Multi...

Страница 42: ...mode rescue operation In this scheme 220V AC UPS ARD provides power supply to the Elevator controller and Inverter for rescue operation during power failure The following below figure shows the wiring...

Страница 43: ...RD provide temporary power supply to the Elevator controller which routes the UPS ARD power supply to MD500L inverter also for Elevator rescue operation When door is fully closed and safeties are conn...

Страница 44: ...ng resistor is not installed 1 Eliminate short circuit 2 Increase the deceleration timeF0 18 3 Check the power supply and ensure it is normal 4 Remove the added load 5 Install the braking resistor Err...

Страница 45: ...ut voltage to within the allowed range 3 to 6 Seek for maintenance Err10 Drive overload 1 The load is too heavy or the rotor is locked 2 The drive is of too small power class 1 Reduce the load or chec...

Страница 46: ...the drive board Err19 Motor tuning fault 1 Motor parameters are wrong 2 Motor tuning overtime 1 Check motor parameters F1 00 to F1 05 2 Check the wiring between drive and motor Err21 EEPROM read write...

Страница 47: ...high Increase the carrier frequency or take other measures to cool the motor Err61 Two or three drive output phases loss 1 The drive output connections get loose 2 The output contactor gets wrongly op...

Страница 48: ...eplace the fan and clean the air filter 3 Seek for maintenance The motor does not rotate after the AC drive outputs a non zero reference 1 The motor or motor cable is damaged 2 The motor parameters ar...

Страница 49: ...the motor is normal Check whether the ventilation is clogged Check whether the ambient temperature is within the permissible range Installation environment Inspect whether the cabinet and cable duct a...

Страница 50: ...cracking occurs on peripheral devices Replace abnormal peripheral devices Ventilation Inspect whether ventilation and heatsink are clogged Check whether the fan is damaged Clean the ventilation Replac...

Страница 51: ...hether there is crack on the blade whether there is abnormal vibration noise upon startup whether the blade runs abnormally Removal 1 Depress the fan cover hook and take the fan cover off the top of t...

Страница 52: ...in the fan power cable Fan power socket 2 Install the fan into the drive and ensure that the mounting pins are aligned Mounting pin x 4 3 Insert the two guide pins into the square holes and then press...

Страница 53: ...e the AC drive to moisture high temperature or outdoor direct sunlight for a long time The electrolytic capacitor will deteriorate after being stored for a long time Therefore the AC drive must be swi...

Страница 54: ...on 2 AI 1 3 AI 2 4 AI 3 6 Multi reference N A 6 F0 07 Frequency source selection 0 Main frequency source X N A 0 F0 09 Rotation direction 0 Same direction 1 Reverse direction N A 0 F0 10 Maximum frequ...

Страница 55: ...resistance asynchronous motor 0 001 to 65 535 AC drive power 55 kW 0 0001 to 6 5535 AC drive power 55 kW 0 F1 07 Rotor resistance asynchronous motor 0 001 to 65 535 AC drive power 55 kW 0 0001 to 6 5...

Страница 56: ...t 150 0 F2 13 Excitation adjustment proportional gain 0 to 20000 N A 2000 F2 14 Excitation adjustment integral gain 0 to 20000 N A 1300 F2 15 Torque adjustment proportional gain 0 to 20000 N A 2000 F2...

Страница 57: ...N A 0 F3 14 Voltage digital setting for V F separation 0 to rated motor voltage V 0 F3 15 Voltage rise time of V F separation 0 0 to 1000 0 s 0 0 F3 18 Overcurrent stall prevention current limit for V...

Страница 58: ...el 20 Command source switchover terminal 1 21 Acceleration Deceleration prohibited 22 PID pause 23 PLC status reset 24 Swing pause 25 Counter input 26 Counter reset 27 Length count input 28 Length res...

Страница 59: ...witchover 47 Emergency stop 48 External STOP terminal 2 49 Deceleration DC braking 50 Clear the current running time 51 Switchover between two line mode and three line mode 52 to 59 Reserved F4 10 DI...

Страница 60: ...tive mode 0 Normal 1 Opposite DI6 active mode 0 Normal 1 Opposite 7 segment 00000 to 11111 binary N A 00000 Group F5 output terminals Parameter Parameter Name Setting Range Unit Default Commission F5...

Страница 61: ...vel detection FDT2 output 26 Frequency 1 reached 27 Frequency 2 reached 28 Current 1 reached 29 Current 2 reached 30 Timing reached 31 AI1 input limit exceeded 32 Load becoming 0 33 Reverse running 34...

Страница 62: ...DC injection 1 active set time 0 0 to 5 0 s 0 5 F6 07 Acceleration Deceleration mode 0 Linear acceleration deceleration 3 S curve acceleration deceleration C N A 3 F6 08 Time proportion of S curve at...

Страница 63: ...ission F8 04 Stop stage deceleration time 0 0 to 6500 0 s 2 0 F8 26 Frequency switchover point between deceleration time 1 and deceleration time 2 0 00 to max frequency Hz 0 00 F8 55 Brake release cur...

Страница 64: ...lay time for rescue operation 0 0 to 20 0 s 0 0 F8 71 Regeneration load slip 50 to 200 100 F8 72 Rescue operation 0 Disable 1 Enable N A 0 F8 73 Rescue direction check time 0 0 to 10 0 s 1 0 F8 75 Res...

Страница 65: ...F9 08 Braking operation voltage level 700 to 800 V 750 F9 09 Fault auto reset times 0 to 20 N A 0 F9 11 Time interval of fault auto reset 0 1 to100 0 s 1 0 F9 13 Drive output phase loss detection enab...

Страница 66: ...ce 2 0 0 to 100 0 11 0 FC 03 Reference 3 0 0 to 100 0 12 0 FC 04 Reference 4 0 0 to 100 0 40 0 FC 05 Reference 5 0 0 to 100 0 13 0 FC 06 Reference 6 0 0 to 100 0 14 0 FC 07 Reference 7 0 0 to 100 0 15...

Страница 67: ...t Commission FP 00 User password 0 to 65535 N A 0 FP 01 Parameter initialization 0 No operation 01 Restore factory settings except motor parameters 02 Clear records 04 Restore user backup parameters 5...

Страница 68: ...put current N A A N A U0 05 Output power N A kW N A U0 06 Output torque N A N A U0 07 DI state N A N A N A U0 08 DO state N A N A N A U0 09 AI1 voltage N A V N A U0 10 AI2 voltage N A V N A U0 11 AI3...

Страница 69: ...R RQH DR DQ LVWULFW 6KHQ KHQ 7HO D 6KHQ KHQ QRYDQFH 7HFKQRORJ R WG ZZZ LQRYDQFH FRP GG 1R RX LDQJ 5RDG XH L 7RZQ X KRQJ LVWULFW 6X KRX 3 5 KLQD 7HO D 6X KRX QRYDQFH 7HFKQRORJ R WG ZZZ LQRYDQFH FRP 190...

Отзывы: