2.1.4 Atmospheric conditions
The ambient air must be clean and relative humidity must not exceed 50% at over 40 °C. Higher levels of relative
humidity, up to 95%, can be tolerated at below 30 °C.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations and, apart from the unit’s own protection, vigilance of these units is necessary once they have been
started up on sites where it is suspected that the conditions described above will not be present.
2.1.5 Pollution degree
The pollution degree for which the units have been designed is level
3
.
2.1.6 Noise pollution
When on, the inverter generates a slight buzzing sound.
Do not place it in an occupied room, or on light supports which might amplify this
buzz. The mounting surface must be firm and appropriate for the weight of the unit.
2.1.7 Ventilation
A clear space must be kept, no less than 30 cm from the top, bottom and sides of the unit, as well as 80 cm from
the front to allow the door to be opened. Only in this way will the unit’s cooling system be able to operate correctly
The units are cooled by forced convection using six fans (three inlet and three outlet) each capable of handling a
flow of 78 m³/h.