Based on the resistive value selected on the installation, the following safe operating areas will be
obtained, within which the Ingecon
®
μWind Interface is able to brake the wind turbine in any wind
conditions.
If the wind turbine is operating outside the area established in the Ingeteam graph, then the Ingecon
®
μWind Interface braking capacity is not guaranteed.
0
5000
10000
15000
20000
25000
30000
35000
40000
0
50.0
100.0
182.0
242.6
303.3
356.3
400.0
R = 3 Ohm
R = 4 Ohm
R = 5 Ohm
R = 6 Ohm
R = 7 Ohm
R = 8 Ohm
R = 9 Ohm
R = 10 Ohm
R = 3 Ohm
R = 4 Ohm
R = 5 Ohm
R = 6 Ohm
R = 7 Ohm
R = 8 Ohm
R = 9 Ohm
R = 10 Ohm
Pe
ak p
ow
er (
W
)
VLL (Vrms)
3 Ohm
4 Ohm
5 Ohm
6 Ohm
7 Ohm
8 Ohm
9 Ohm
10 Ohm
Peak power
(W)
19200
25600
32000
36816.7
31557.1
27612.5
24544.4
22090
VLL (Vrms)
182
242.6
303.3
356.3
356.3
356.3
356.3
356.3
Connection
1.
The braking resistors shall be connected at the R.OUT terminal as shown below
2.
Check that the cable terminals have been correctly tightened at the connector terminals.
3.
Tighten the cable glands to ensure that the equipment is airtight.
The cable diameter of the resistors must not be greater than 17 mm.
5.3.8. Connection to the wind turbine
When connecting the equipment to the wind turbine, the connections to be made will depend on whether the wind
turbine output voltage is DC or AC. Each situation has a different procedure.