User Manual V1.3 | XtracontrolDC2, XtracontrolET2, XtracontrolEC21
5.1.1
Connecting the power supply to the XtracontrolDC2 and XtracontrolEC21
CAUTION
Live parts!
▶
Before starting any work on the device, switch off all power feeds,
including peripherals.
▶
Connect the power supply to plug X1 according to the following table.
Fig. 14: Power supply to the XtracontrolDC2 and XtracontrolEC21 plug X1 with power LED
Power supply plug X1
Pin
Designati
on
Assignment
1…8
I/O
Digital inputs and outputs
(see “Digital inputs and outputs, XtracontrolDC2 and XtracontrolEC21”)
9
L1+
Feed to digital output (max. 2 A) for I/O
10
L+ 24 V
Power supply 24 V DC (–15 %/+20 %) (PLC internal processing) max. 1.2 A
11
L+ 24 V
Power supply 24 V DC (–15 %/+20 %) (PLC internal processing) max. 1.2 A
12
GND
–
The following counterparts have been tested for the SC-SMT 3.5 (Weidmüller) plug-in connector and are approved
for use with the device:
BLZF 3.50/12/180
28
©
Infranor GmbH
Содержание Xtracontrol DC2
Страница 1: ......