User Manual V1.3 | XtracontrolDC2, XtracontrolET2, XtracontrolEC21
5.2.8
Serial interfaces
The module has two serial communications interfaces (1x RS-232 and 1x RS-485), which are connected via the
common RJ45 plug X6.
Maximum baud rate for both interfaces: 115 kBd
Fig. 26: RS-232 / RS-485 interface X6
Pin assignment for RS-232 / RS-485 interface plug X6
Pin
Assignment / software interface
Pin
Assignment / software interface
1
RS-232 RX / COM 1
5
RS-485 Tx/Rx– / COM 2
2
RS-232 TX / COM 1
6
NC
3
NC
7
(reserved)
4
RS-485 Tx/Rx+ / COM 2
8
ISO GND
The RS-485 interface is “soft” terminated in the dialogue controller with 560 .
Ω
If the interface is located at the start or end of the bus topology:
▶
Set switch S3 to ON in order to switch on the 120 terminating resistor.
Ω
Fig. 27: RS-485 switchable terminating resistor
As far as possible, the assignment of the interfaces should be carried out in accordance with the
specifications given in “MODBUS over Serial Line; Specification and Implementation Guide V1.02”.
© Infranor GmbH
41
Содержание Xtracontrol DC2
Страница 1: ......