LT 6541 (Iss 4 07/14)
15
INFINITY 890 BF
Installation Instructions
SECTION SEVEN
Siting the Appliance
(When installing in a timber framed dwelling reference must be made to the specific installation
requirements stated in
Section 9 Installing the Appliance in Timber Framed Dwelling
).
GENERAL REQUIREMENTS
The flue and air duct length must be between 100mm to 1000mm.
The fire is supplied with a standard pipe length of 535mm ( to be cut in half to make a flue duct
and air duct length of 267.5mm.) The 535mm length of flue can be cut down as required.
The flue and air duct must not have any bends.
The flue outlet must terminate on a suitable outside wall.
The minimum flue terminal clearances, which must be maintained, are as shown below.
A
Directly below an openable window or other opening. E.g. air brick
300mm
B
Below gutters, soil pipes or drain pipes
300mm
C
Below eaves
300mm
D
Below balconies or carport roofs
600mm
E
From vertical drain pipes and soil pipes
75mm
F
From internal and external corners
300mm
G
Above ground, roof or balcony level
370mm
H
From a surface facing the terminal
600mm
I
From a terminal facing the terminal
1200mm
J
From an opening in a car port into a dwelling e.g. door, window, etc
1200mm
K
Vertically from a terminal on the same wall
1500mm
L
Horizontally from a terminal on the same wall
300mm