Parameter Description
Default
Min
Max
M07
Analogue input 1 function:
0=Remote regulation sensor
1=Water sensor for automatic season changeover
2=Minimum thermostat sensor (fancoil water coil)
3=Season changeover remote contact (INPUT ON=winter, INPUT OFF=summer)
4=Remote On/Off
5=Not occupied holidays (INPUT ON=occupied)
6=Economy (INPUT ON=economy on)
7=Window contact (INPUT OFF=window open)
8=Alarm (INPUT ON=alarm present)
9=Not used
9
0
9
M08
Analogue input 1 logic (only with
M07
=3...8):
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1=Normally closed (closed=INPUT OFF, open=INPUT ON)
0
0
1
M09
Analogue input 2 function:
0=Remote regulation sensor
1=Water sensor for automatic season changeover
2=Minimum thermostat sensor (fancoil water coil)
3=Season changeover remote contact (INPUT ON=winter, INPUT OFF=summer)
4=Remote On/Off
5=Not occupied holidays (INPUT ON=occupied)
6=Economy (INPUT ON=economy on)
7=Window contact (INPUT OFF=window open)
8=Alarm (INPUT ON=alarm present)
9=Not used
9
0
9
M10
Analogue input 2 logic (only with
M09
=3...8):
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1=Normally closed (closed=INPUT OFF, open=INPUT ON)
0
0
1
M11
Analogue input 3 function:
0=Remote regulation sensor
1=Water sensor for automatic season changeover
2=Minimum thermostat sensor (fancoil water coil)
3=Season changeover remote contact (INPUT ON=winter, INPUT OFF=summer)
4=Remote On/Off
5=Not occupied holidays (INPUT ON=occupied)
6=Economy (INPUT ON=economy on)
7=Window contact (INPUT OFF=window open)
8=Alarm (INPUT ON=alarm present)
9=Not used
10=Input 0...10V (Jumper JP1 must be set on 2-3 (0...10V))
9
0
10
M12
Analogue input 3 logic (only with
M11
=3...8):
0=Normally open (open=INPUT OFF, closed=INPUT ON)
1=Normally closed (closed=INPUT OFF, open=INPUT ON)
0
0
1
M13
Motor type
0=EC motor
1=3 speed on-off motor
0
0
1
M14
EC motor type
0=EC motor with auxiliary relay
1=standard EC motor
0
0
1
M15
Half season function enable
Determines whether to enable the electric resistance for
M01
=5, 6 and 7 operation on models
TH-0xxSx1
,
TH-1xxSx1
,
TH-2xxSx1
(
M13
=0),
TH-4xxSx1
.
0=half season function not enabled
1=half season function enabled In cooling mode, you can use the electric resistance for heating if
the temperature drops below the setpoint (see heating/cooling 2 pipe + electric resistance (
M01
=5, 6,
7) for the models indicated)
1
0
1